  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Setting frequency

    Set Pr.52 (DU/PU main display data selection) to "5".This allows for displaying the setting frequency on the voltage monitor.Then, switch to the monitor mode... More Details >>

    • No:21784
    • Release Date:2018/08/22 16:29
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29
  • Connecting ammeter to output side

    Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>

    • No:21681
    • Release Date:2018/08/22 16:28
  • Frequency setting signal

    Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>

    • No:21265
    • Release Date:2018/08/22 16:26
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Terminal

    Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>

    • No:21679
    • Release Date:2018/08/22 16:28
  • Brake unit

    The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>

    • No:21328
    • Release Date:2018/08/22 16:27
  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Input phase loss

    The detection time 1 s cannot be changed. More Details >>

    • No:21277
    • Release Date:2018/08/22 16:26