  • Display unit of operation panel

    Set the rotations per minute that is obtained while operating at the frequency set with Pr.505 (Speed setting reference) to Pr.37 (Speed display).For example... More Details >>

    • No:21774
    • Release Date:2018/08/22 16:29
  • Model setting in FR-Configurator

    Check the version of FR-Configurator (FR-SW3-SETUP-WJ). If the version is "1.00", it does not support or detect the FR-E740. Version "2.00" supports the FR-E... More Details >>

    • No:21309
    • Release Date:2018/08/22 16:26
  • Operation mode setting

    To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>

    • No:21852
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>

    • No:21800
    • Release Date:2018/08/22 16:29
  • Frequency setting

    If Pr.79 (Operation mode) is set to "0" (PU/EXT switching mode), press the PU/EXT button on the operation panel to turn on the PU LED.Turn the setting dial t... More Details >>

    • No:21855
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Parameter copy of FR-Configurator

    The parameter can be copied to only one inverter. More Details >>

    • No:21306
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Use Pr.125 (Terminal 2 frequency setting gain frequency).  More Details >>

    • No:21913
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Yes.The inverter requires the start signal and frequency setting signal. More Details >>

    • No:21793
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29