  • Switching between External operation mode and PU operation mode

    Assign X16 signal, and set Pr.79 to "0", to switch the operation mode with turning ON/OFF X16 signal. More Details >>

    • No:21288
    • Release Date:2018/08/22 16:26
  • Electronic thermal O/L relay

    Check that the correct rated motor current is set in Pr.9 (Electronic thermal O/L relay). No parameter is available for setting the operation time of the ele... More Details >>

    • No:21291
    • Release Date:2018/08/22 16:26
  • Printing (character size) of FR-Configurator

    The size of the fonts are bigger to make it easy to read in Ver.2.01 of FR-Configurator (FR-SW3-SETUP-WJ). Download the latest version from the Mitsubishi El... More Details >>

    • No:21316
    • Release Date:2018/08/22 16:27
  • Terminal indicator lamp

    The inverter outputs the peak voltage 300 to 400 VDC of the bus voltage not in a pure sine wave but a in a PWM waveform. Check if the lamp to be connected ca... More Details >>

    • No:21323
    • Release Date:2018/08/22 16:27
  • Instruction manual

    For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>

    • No:21341
    • Release Date:2018/08/22 16:27
  • Network operation

    Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>

    • No:21674
    • Release Date:2018/08/22 16:28
  • Terminal

    Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>

    • No:21679
    • Release Date:2018/08/22 16:28
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • Connecting ammeter to output side

    Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>

    • No:21681
    • Release Date:2018/08/22 16:28
  • PU operation

    Set Pr.40 (RUN key rotation direction selection) to "1" (Reverse). More Details >>

    • No:21693