FAQ within [ FREQROL-F700PJ ]

91-100 of Total 251

prev 10 / 26page next
  • Control terminal

    Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>

    • No:21845
    • Release Date:2018/08/22 16:29
  • PU operation

    Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21863
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Use Pr.125 (Terminal 2 frequency setting gain frequency).  More Details >>

    • No:21913
    • Release Date:2018/08/22 16:30
  • Countermeasure against noises

    Yes. The carrier frequency can be decreased by the setting of Pr.72 (PWM frequency selection). More Details >>

    • No:21338
    • Release Date:2018/08/22 16:27
  • Full scale frequency

    You can change the full-scale value by changing Pr.55 (Frequency monitor reference). The initial setting is 60 Hz. More Details >>

    • No:21672
    • Release Date:2018/08/22 16:28
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • FR-Configurator

    Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it.   More Details >>

    • No:21711
    • Release Date:2018/08/22 16:29
  • Parameter

    No parameter can be used to directly set this time.Changing Pr.9 (Electronic thermal O/L relay) changes the time. More Details >>

    • No:21769
    • Release Date:2018/08/22 16:29
  • Running frequency

    Check the setting of Pr.1 (Maximum frequency) and Pr.18 (High speed maximum frequency).Pr.1 is initially set to "120 Hz". More Details >>

    • No:21821
    • Release Date:2018/08/22 16:29
  • FR-PA07

    Since the multi-speed is given a higher priority, the setting by the setting dial is not enabled unless all of the multi-speed signals are OFF. More Details >>

    • No:21302
    • Release Date:2018/08/22 16:26