  • Auto tuning

    Normally, the auto tuning condition depends on the combination of the inverter and motor (including wiring to the motor), perform auto tuning each time. The ... More Details >>

    • No:21293
    • Release Date:2018/08/22 16:26
  • Frequency setting

    The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>

    • No:21858
    • Release Date:2018/08/22 16:29
  • Running frequency

    The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>

    • No:21820
    • Release Date:2018/08/22 16:29
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can use the setting dial to set the frequency during operation even if Pr.77 is not set to "2".Setting Pr.77 to "2" allows for changing the parameter set... More Details >>

    • No:21786
    • Release Date:2018/08/22 16:29
  • Frequency

    It seems that calibration for 20 mA current signal input is not correct.Use the calibration parameters "126" and "C7" to calibrate the inverter.Perform calib... More Details >>

    • No:21785
    • Release Date:2018/08/22 16:29
  • Output current value

    The detection level of the output current value cannot be changed using a potentiometer or a similar device.   More Details >>

    • No:21779
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>

    • No:21685
    • Release Date:2018/08/22 16:28
  • Electronic thermal O/L relay setting

    When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>

    • No:21676
    • Release Date:2018/08/22 16:28