  • FR-PA07

    Since the multi-speed is given a higher priority, the setting by the setting dial is not enabled unless all of the multi-speed signals are OFF. More Details >>

    • No:21302
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Set C5 (Pr.904) (Terminal 4 frequency setting bias frequency) to 0 Hz and Pr.126 (Terminal 4 frequency setting gain frequency) to 50 Hz. More Details >>

    • No:21268
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Check that the wiring of the terminal 4 and 5 are not reversed. More Details >>

    • No:21266
    • Release Date:2018/08/22 16:26
  • Operation method

    Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>

    • No:21249
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>

    • No:21915
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can use the setting dial together with the terminal 4.Set Pr.79 (Operation mode) to "3" (Combined operation mode) and assign the AU signal to an unused t... More Details >>

    • No:21856
    • Release Date:2018/08/22 16:29
  • Frequency setting

    If Pr.79 (Operation mode) is set to "0" (PU/EXT switching mode), press the PU/EXT button on the operation panel to turn on the PU LED.Turn the setting dial t... More Details >>

    • No:21855
    • Release Date:2018/08/22 16:29
  • Operation panel

    Since the operation panels of the E700, D700, and F700PJ do not have keys for the forward (FWD) and reverse (REV) rotations, you can only command rotation in... More Details >>

    • No:21841
    • Release Date:2018/08/22 16:29
  • Running frequency

    The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>

    • No:21820
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21792
    • Release Date:2018/08/22 16:29