- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700PJ
FAQ
Keyword Search
FAQ within [ FREQROL-F700PJ ]
-
Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>
- No:21286
- Release Date:2018/08/22 16:26
-
Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>
- No:21267
- Release Date:2018/08/22 16:26
-
Transistor output module of the programmable controller
Check if signals that are ON when the programmable controller's transistor output starts are always ON. More Details >>
- No:21811
- Release Date:2018/08/22 16:29
-
The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current signa... More Details >>
- No:21800
- Release Date:2018/08/22 16:29
-
You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>
- No:21787
- Release Date:2018/08/22 16:29
-
1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>
- No:21359
- Release Date:2018/08/22 16:27
-
It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>
- No:21322
- Release Date:2018/08/22 16:27
-
Printing (character size) of FR-Configurator
The size of the fonts are bigger to make it easy to read in Ver.2.01 of FR-Configurator (FR-SW3-SETUP-WJ). Download the latest version from the Mitsubishi El... More Details >>
- No:21316
- Release Date:2018/08/22 16:27
-
The detection time 1 s cannot be changed. More Details >>
- No:21277
- Release Date:2018/08/22 16:26
-
The power supply voltage may have dropped.Read the converter output voltage monitor (Pr.55 = 8) and check if Converter output voltage monitor/√2 is within th... More Details >>
- No:21820
- Release Date:2018/08/22 16:29