  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>

    • No:21722
    • Release Date:2018/08/22 16:29
  • Motor specifications setting

    Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>

    • No:21717
    • Release Date:2018/08/22 16:29
  • Offline auto tuning

    When auto tuning completes normally, the setting value of Pr.96 (Auto tuning setting/status) is changed to "3". When it is not changed, check the set paramet... More Details >>

    • No:21353
    • Release Date:2018/08/22 16:27
  • Rated frequency setting

    Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>

    • No:21280
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>

    • No:21265
    • Release Date:2018/08/22 16:26
  • Driving a single-phase motor

    No, it cannot. More Details >>

    • No:21253
    • Release Date:2018/08/22 16:26
  • Frequency command

    Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>

    • No:21251
    • Release Date:2018/08/22 16:26
  • Frequency setting

    You can connect up to three inverters to a single external frequency setting potentiometer to control them.   More Details >>