FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700PJ
FAQ
Keyword Search
FAQ within [ FREQROL-F700PJ ]
-
No, it cannot. More Details >>
- No:21253
- Release Date:2018/08/22 16:26
-
The operation panels of the FR-E700, FR-D700, and FR-F700PJ are not detachable.Therefore, it cannot be attached to the enclosure surface.You can use the opti... More Details >>
- No:21851
- Release Date:2018/08/22 16:29
-
With the monitor indicator "1", there is no problem with the parameter setting of auto tuning. Check if the terminals MRS and SD are not shortened in the wir... More Details >>
- No:21294
- Release Date:2018/08/22 16:26
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21730
- Release Date:2018/08/22 16:29
-
When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>
- No:21283
- Release Date:2018/08/22 16:26
-
Number of stations that can be set in FR Configurator
The station numbers that can be set differ depending on the version of FR-Configurator (FR-SW3-SETUP-WJ) setup software. For Ver.2.00 or later, station numbe... More Details >>
- No:21305
- Release Date:2018/08/22 16:26
-
Setting dial and FR-PA02 built-in potentiometer
When the FR-PA02 is connected to the inverter with a cable, the FR-PA02 becomes effective.The operation panel of the inverter can also be used to set some pa... More Details >>
- No:21861
- Release Date:2018/08/22 16:29
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
Basically it is not possible due to the operation command source.However, if Pr.77 (Parameter write selection) is set to "2", you can use both the FR-PA07 an... More Details >>
- No:21698
- Release Date:2018/08/22 16:28
-
Auto tuning can help to apply appropriate voltage to the load and decrease the current. Since the electronic thermal O/L relay trips, check that the rated mo... More Details >>
- No:21292
- Release Date:2018/08/22 16:26
11-20 of Total 252