FAQ within [ FREQROL-F700PJ ]
-
As the AS-OX has the "0ADJ" potentiometer for frequency meter calibration, use it to adjust the meter so that both readings match. More Details >>
- No:21795
- Release Date:2018/08/22 16:29
-
1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>
- No:21718
- Release Date:2018/08/22 16:29
-
Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>
- No:21717
- Release Date:2018/08/22 16:29
-
1. Yes. 2. The standard set by Pr.56. More Details >>
- No:21669
- Release Date:2018/08/22 16:28
-
While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>
- No:21919
- Release Date:2018/08/22 16:30
-
Transistor output module of the programmable controller
Check if signals that are ON when the programmable controller's transistor output starts are always ON. More Details >>
- No:21811
- Release Date:2018/08/22 16:29
-
Connect the brake resistor to the terminal P and terminal PR. (For the FR-A700-7.5K or lower, remove the jumper of the terminals PR and PX.) Do not remove th... More Details >>
- No:21333
- Release Date:2018/08/22 16:27
-
Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>
- No:21330
- Release Date:2018/08/22 16:27
-
Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>
- No:21286
- Release Date:2018/08/22 16:26
-
If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>
- No:21343
- Release Date:2018/08/22 16:27