It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>
- No:21247
- Release Date:2018/08/22 16:26
-
You need to press the "SET" key with the initial setting.The frequency is not set unless you press the "SET" key.Setting Pr.161 (Frequency setting/key lock o... More Details >>
- No:21735
- Release Date:2018/08/22 16:29
-
Switching between external operation and NET operation
You can monitor the fault output in both NET operation and external operation. More Details >>
- No:21686
- Release Date:2018/08/22 16:28
-
No, it cannot. More Details >>
- No:21253
- Release Date:2018/08/22 16:26
-
Setting dial and FR-PA02 built-in potentiometer
When the FR-PA02 is connected to the inverter with a cable, the FR-PA02 becomes effective.The operation panel of the inverter can also be used to set some pa... More Details >>
- No:21861
- Release Date:2018/08/22 16:29
-
No.Just turn the setting dial to select a frequency and press the "SET" key, and the inverter operates at the selected frequency. More Details >>
- No:21798
- Release Date:2018/08/22 16:29
-
You can do so by setting Pr.73 to "10" or "11". (For A700/F700 (P), supply negative input to the terminal 1.) More Details >>
- No:21908
- Release Date:2018/08/22 16:30
-
Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>
- No:21717
- Release Date:2018/08/22 16:29
-
Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>
- No:21679
- Release Date:2018/08/22 16:28
-
The forward rotation and reverse rotation are enabled by pressing the FWD/REV key on the operation panel. More Details >>