Setting dial and FR-PA02 built-in potentiometer
When the FR-PA02 is connected to the inverter with a cable, the FR-PA02 becomes effective.The operation panel of the inverter can also be used to set some pa... More Details >>
- No:21861
- Release Date:2018/08/22 16:29
-
Transistor output module of the programmable controller
Check if signals that are ON when the programmable controller's transistor output starts are always ON. More Details >>
- No:21811
- Release Date:2018/08/22 16:29
-
The operation panel FR-PA02 requires the optional FR-E5P (control panel rear cover and adapter set) and connection cable FR-CB20□. Check that Pr.146 (Built-i... More Details >>
- No:21367
- Release Date:2018/08/22 16:27
-
It is set to "1" (cooling fan ON-OFF control enabled). More Details >>
- No:21131
- Release Date:2018/08/22 16:26
-
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>
- No:21675
- Release Date:2018/08/22 16:28
-
It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>
- No:21180
- Release Date:2018/08/22 16:26
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
-
Connecting it causes no problem. More Details >>
- No:21671
- Release Date:2018/08/22 16:28
-
1. Yes. 2. The standard set by Pr.56. More Details >>
- No:21669
- Release Date:2018/08/22 16:28