When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
Blinking of the "RUN" LED on the panel suggests that the frequency command may not be input. Create a frequency setting data as for the forward rotation comm... More Details >>
Set Pr.56 (Current monitor reference) to "10A". More Details >>
Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency). More Details >>
You can perform forward and reverse operations with the RUN key on the operation panel by setting Pr.40 (RUN key rotation direction selection). More Details >>
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>
Switching between external operation ...
You can switch between external operation and NET operation by turning ON/OFF the terminal X66 (RM). You can switch while Pr.79 (Operation mode) is set to "6... More Details >>
Switching between external operation ...
You can write frequency setting by setting Pr.339 (Communication speed command source) to "0". More Details >>
Yes, you can set Pr.20 to 20 Hz. More Details >>