  • FR-Configurator

    Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it.   More Details >>

    • No:21711
    • Release Date:2018/08/22 16:29
  • Frequency setting

    The full scale of the frequency is initially set to 60 Hz and the frequency indication becomes the full scale at 60 Hz operation.To change the indication val... More Details >>

    • No:21866
    • Release Date:2018/08/22 16:29
  • Motor: SF-HJCA

    Configure the same setting as the SF-HRCA. Configure the same setting as the SF-HRCA. A700, E700, D700, F700PJ: Pr.71 = 50F700P, F700: Pr.71 = 1 (Reference) ... More Details >>

    • No:21136
    • Release Date:2018/08/22 16:26
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Switching External operation, PU operation

    Setting Pr.79 (Operation mode) to "6" sets the switchover mode. Pressing the "PU/EXT" key on the operation panel during External operation switches the mode ... More Details >>

    • No:21289
    • Release Date:2018/08/22 16:26
  • Installation direction

    Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>

    • No:21286
    • Release Date:2018/08/22 16:26
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Start command

    Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>

    • No:21285
    • Release Date:2018/08/22 16:26
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27