Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>
- No:21788
- Release Date:2018/08/22 16:29
-
Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>
- No:21249
- Release Date:2018/08/22 16:26
-
When the pulse is counted and displayed, 1440 pulses are output with the frequency of the inverter is 60 Hz. Since these pulses are limited to 2400 pulses, a... More Details >>
- No:21334
- Release Date:2018/08/22 16:27
-
You can do so by assigning the terminal AU.Assign the terminal AU to an unused terminal.(For example, when assigning AU to the terminal RL, set Pr.180 = 4.)B... More Details >>
- No:21915
- Release Date:2018/08/22 16:30
-
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
- No:21845
- Release Date:2018/08/22 16:29
-
No.Just turn the setting dial to select a frequency and press the "SET" key, and the inverter operates at the selected frequency. More Details >>
- No:21798
- Release Date:2018/08/22 16:29
-
It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>
- No:21180
- Release Date:2018/08/22 16:26
-
External installationRated current
Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>
- No:21817
- Release Date:2018/08/22 16:29
-
Number of stations that can be set in FR Configurator
The station numbers that can be set differ depending on the version of FR-Configurator (FR-SW3-SETUP-WJ) setup software. For Ver.2.00 or later, station numbe... More Details >>
- No:21305
- Release Date:2018/08/22 16:26
-
Fault output terminal A, B, and C
Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>
- No:21324
- Release Date:2018/08/22 16:27