Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>
- No:21725
- Release Date:2018/08/22 16:29
-
Automatic restart after instantaneous power failure setting
You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>
- No:21731
- Release Date:2018/08/22 16:29
-
Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>
- No:21732
- Release Date:2018/08/22 16:29
-
Change the value of Pr.18 (High speed maximum frequency).You can set any frequency within the range defined by Pr.18. More Details >>
- No:21737
- Release Date:2018/08/22 16:29
-
Press the "SET" key once while the output frequency is monitored.The unit indicator LED changes from "Hz" to "A" and the monitor display changes to the current. More Details >>
- No:21764
- Release Date:2018/08/22 16:29
-
Multi-speed setting and external potentiometer
The multi-speed setting is prioritized.The external potentiometer setting is effective when the multi-speed signal is not input. More Details >>
- No:21773
- Release Date:2018/08/22 16:29
-
Yes.The inverter requires the start signal and frequency setting signal. More Details >>
- No:21793
- Release Date:2018/08/22 16:29
-
When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>
- No:21794
- Release Date:2018/08/22 16:29
-
Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>
- No:21803
- Release Date:2018/08/22 16:29
-
In this case, the JOG operation is prioritized.When the terminals JOG and SD are short-circuited and turned ON, the frequency setting by the external potenti... More Details >>
- No:21804
- Release Date:2018/08/22 16:29