Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F700PJ ]

71-80 of Total 252

prev 8 / 26page next
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • External installationRated current

    Since the external thermal prevents the motor from being overheated, install it between the output terminal of the inverter and the motor.The rated current i... More Details >>

    • No:21817
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>

    • No:21794
    • Release Date:2018/08/22 16:29
  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • FR-PA07

    No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>

    • No:21365
    • Release Date:2018/08/22 16:27
  • Output frequency

    In the initial setting, it is set to 120 Hz. More Details >>

    • No:21345
    • Release Date:2018/08/22 16:27
  • Instruction manual

    For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>

    • No:21341
    • Release Date:2018/08/22 16:27
  • Frequency setting

    This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>

    • No:21843
    • Release Date:2018/08/22 16:29

71-80 of Total 252