FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E500
FAQ
Keyword Search
FAQ within [ FREQROL-E500 ]
-
Speed control failure due to 20 mA from DC 4
It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>
- No:21998
- Release Date:2018/08/22 16:30
-
Err display on operation panel
The following causes are probable for this Err display:- Operation error (for example, you tried to input a value other than the available range of parameter... More Details >>
- No:22063
- Release Date:2018/08/22 16:30
-
Parameter No.79 (Operation mode)
You cannot cancel multi-speed command input. When the multi-speed command is input from the terminal, you cannot use the potentiometer. Use the inverter so t... More Details >>
- No:21467
- Release Date:2018/08/22 16:27
-
Using the inverter's input terminal, you can use up to 15 speeds.This function is supported by the current 500 series products (A500, F500, E500, and S500).U... More Details >>
- No:21947
- Release Date:2018/08/22 16:30
-
UL standard certification number
The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>
- No:21506
- Release Date:2018/08/22 16:28
-
1. To perform emergency stop, it is recommended to have the motor coast and stop it using a mechanical brake.In this case, the output stop (MRS) signal is in... More Details >>
- No:22103
- Release Date:2018/08/22 16:31
-
Difference between SU (up to frequency) and FU (frequency detection)
- SU signal (up to frequency signal)This signal is output when the inverter output frequency reaches the set frequency (the frequency the inverter is require... More Details >>
- No:21436
- Release Date:2018/08/22 16:27
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
-
The following causes are probable for persistent Err. display: 1. The terminals RES and SD are always short-circuited. 2. Operation panel contact or operatio... More Details >>
- No:21412
- Release Date:2018/08/22 16:27
-
An inverter is used to rotate a motor but it cannot be used to detect whether the belt is broken or not. However, the magnitude of the load will change when ... More Details >>
- No:21387
- Release Date:2018/08/22 16:27
11-20 of Total 85