FAQ within [ FREQROL-E500 ]
-
"Err" is displayed when STF signal turns ON
Possible causes are:1. The reset signal (RES) is ON. 2. The built-in CPU is not working properly due to contact faults of the inverter parts. Check the exte... More Details >>
- No:21484
- Release Date:2018/08/22 16:27
-
Speed change due to power supply voltage fluctuation
1. The output frequency satisfies the "control specification/frequency precision" even when the power supply voltage changes, but the output voltage cannot r... More Details >>
- No:22069
- Release Date:2018/08/22 16:30
-
When the wire between the 400 V inverter and motor is long (20 m or longer), surge voltage occurs momentarily. This voltage is as two or more times as the DC... More Details >>
- No:21404
- Release Date:2018/08/22 16:27
-
Surge voltage of 400 V inverter
No. Although the carrier frequency increases or decreases the switching count, the switching speed is the OFF-to-ON speed of the IGBT element of the inverter... More Details >>
- No:21401
- Release Date:2018/08/22 16:27
-
Using the inverter's input terminal, you can use up to 15 speeds.This function is supported by the current 500 series products (A500, F500, E500, and S500).U... More Details >>
- No:21947
- Release Date:2018/08/22 16:30
-
UL standard certification number
The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>
- No:21506
- Release Date:2018/08/22 16:28
-
Inverter drive of 400 V class motor
When the wiring between the inverter and motor is long, surge voltage occurs at the terminal of the motor.This surge voltage deteriorates insulation of the m... More Details >>
- No:21926
- Release Date:2018/08/22 16:30
-
The following causes are probable for persistent Err. display: 1. The terminals RES and SD are always short-circuited. 2. Operation panel contact or operatio... More Details >>
- No:21412
- Release Date:2018/08/22 16:27
-
Speed control failure due to 20 mA from DC 4
It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>
- No:21998
- Release Date:2018/08/22 16:30
-
Frequent occurrences of OL means that the inverter is overloaded. Since the inverter can go faulty if it is constantly overloaded, you need to take a counter... More Details >>
- No:21430
- Release Date:2018/08/22 16:27
11-20 of Total 85