- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E500
FAQ
Keyword Search
FAQ within [ FREQROL-E500 ]
-
Although you specify the FR-V200 and others as the inverter models, CC-Link is currently supported by the FR-A500 and FR-E500. The FR-V200E does not support ... More Details >>
- No:21499
- Release Date:2018/08/22 16:27
-
Built-in potentiometer and current input switching control
For setting the frequency, you cannot switch between the operation panel potentiometer and current input from an external source.To switch between the extern... More Details >>
- No:21985
- Release Date:2018/08/22 16:30
-
Ensure that the inverter is in the PU operation mode and stopped, change the following parameters: 1. Read Pr.923 (Built-in frequency setting potentiometer g... More Details >>
- No:21416
- Release Date:2018/08/22 16:27
-
Connection with personal computer
Connection method for the A500 and E500 is shown in the figure below. The figure is given in an Excel file. Figure 1 More Details >>
- No:21536
- Release Date:2018/08/22 16:28
-
I want to synchronize the Z200 and E500.
If you are using analog voltage commands, connect the voltage inputs to the FR-E500 and FR-Z200 in parallel to equalize inputs to both units and speeds are s... More Details >>
- No:21929
- Release Date:2018/08/22 16:30
-
Speed 2 operation with potentiometer on operation panel
Yes. Set parameters as below.For FR-E500Set Pr.79 =3, and Pr.146= 0.Multi-speed is prioritized.For FR-S500Set Pr.79 = 3, and Pr.53 = 1.Multi-speed is priorit... More Details >>
- No:21963
- Release Date:2018/08/22 16:30
-
Notes when inverter capacity is larger than motor capacity
When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>
- No:22040
- Release Date:2018/08/22 16:30
-
Operation panel extension cable
Yes, you can use the 10BASE-T cable (straight) with the E500. More Details >>
- No:22085
- Release Date:2018/08/22 16:30
-
1. Pr.146 is not available. Some catalogs and manuals cover this parameter, but it is an error. The latest catalogs and manuals have been corrected to el... More Details >>
- No:21529
- Release Date:2018/08/22 16:28
-
When consuming the regenerative power with the brake resistor, the brake transistor is triggered at a certain voltage to make the brake resistor use the rege... More Details >>
- No:22074
- Release Date:2018/08/22 16:30
21-30 of Total 85