FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E500
FAQ
Keyword Search
FAQ within [ FREQROL-E500 ]
-
Speed 2 operation with potentiometer on operation panel
Yes. Set parameters as below.For FR-E500Set Pr.79 =3, and Pr.146= 0.Multi-speed is prioritized.For FR-S500Set Pr.79 = 3, and Pr.53 = 1.Multi-speed is priorit... More Details >>
- No:21963
- Release Date:2018/08/22 16:30
-
CC-Link monitor and parameter setting
1. Since you can monitor the output frequency independently, you do not need to switch monitoring by the monitor commands. Assign the remote register RWr0 to... More Details >>
- No:21418
- Release Date:2018/08/22 16:27
-
1. Can I set the frequency by the external potentiometer when multi-speed signal is 0 (nothing is input)?-> It is possible by using the external operation... More Details >>
- No:21990
- Release Date:2018/08/22 16:30
-
Driving 200 V motor by 400 V inverter
Your suggested use is not recommended due to the following reasons: Output voltage of the 400 V inverter contains "micro surge". Usually this surge voltage i... More Details >>
- No:21403
- Release Date:2018/08/22 16:27
-
1. Pr.146 is not available. Some catalogs and manuals cover this parameter, but it is an error. The latest catalogs and manuals have been corrected to el... More Details >>
- No:21529
- Release Date:2018/08/22 16:28
-
The internal processing speed is not published. The analog input specifications are as follows: FR-A500???1/4000FR-E500???1/1000MR-H???1/4000 More Details >>
- No:21550
- Release Date:2018/08/22 16:28
-
Be sure to use the FR-E5P to mount the operation panel.This is because the board is bare on the back of the operation panel and a dedicated connector is requ... More Details >>
- No:22030
- Release Date:2018/08/22 16:30
-
Setting Pr.37 to the machine speed at 60 Hz switches the frequency monitor to the rotations per minute monitor.Note that the speed setting must be input in a... More Details >>
- No:22072
- Release Date:2018/08/22 16:30
-
"PS" appears when the STOP key on the operation panel is pressed during external operation. It is considered that someone pressed the key. Dismiss "PS" in on... More Details >>
- No:21478
- Release Date:2018/08/22 16:27
-
Countermeasures when input power supply is turned off upon equipment fault
1. When the inverter power supply is turned OFF, the inverter is disconnected from the CC-Link network. However, since the CC-Link master station has the aut... More Details >>
- No:21390
- Release Date:2018/08/22 16:27