Driving 200 V motor by 400 V inverter
Your suggested use is not recommended due to the following reasons: Output voltage of the 400 V inverter contains "micro surge". Usually this surge voltage i... More Details >>
- No:21403
- Release Date:2018/08/22 16:27
-
Connecting the brake resistor allows for quick deceleration because the regenerative power is processed. (The brake torque increases.)Therefore, when an exte... More Details >>
- No:22045
- Release Date:2018/08/22 16:30
-
Countermeasure against the instantaneous power failure with the inverter
The power cannot be supplied to the control power supply separately for the FR-A024/A044 and small type FR-E500. Therefore, the UPS is not available. More Details >>
- No:21368
- Release Date:2018/08/22 16:27
-
General-purpose magnetic flux vector control is effective at low speed under a heavy load.To shorten the acceleration time, use Pr.44 to set the second accel... More Details >>
- No:22059
- Release Date:2018/08/22 16:30
-
When consuming the regenerative power with the brake resistor, the brake transistor is triggered at a certain voltage to make the brake resistor use the rege... More Details >>
- No:22074
- Release Date:2018/08/22 16:30
-
1. To perform emergency stop, it is recommended to have the motor coast and stop it using a mechanical brake.In this case, the output stop (MRS) signal is in... More Details >>
- No:22103
- Release Date:2018/08/22 16:31
-
Notes when inverter capacity is larger than motor capacity
When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>
- No:22040
- Release Date:2018/08/22 16:30
-
If you are using an external VR, influence by noise is probable.Setting Pr.74 (Input filter time constant) to a higher value stabilizes the frequency command... More Details >>
- No:22061
- Release Date:2018/08/22 16:30
-
1. Pr.146 is not available. Some catalogs and manuals cover this parameter, but it is an error. The latest catalogs and manuals have been corrected to el... More Details >>
- No:21529
- Release Date:2018/08/22 16:28
-
If the MC on the input side is shut off using the fault output of the FR-E500, the inverter's fault records are left in the faults history. More Details >>
- No:22096
- Release Date:2018/08/22 16:30
21-30 of Total 84