  • Speed 2 operation with potentiometer on operation panel

    Yes. Set parameters as below.For FR-E500Set Pr.79 =3, and Pr.146= 0.Multi-speed is prioritized.For FR-S500Set Pr.79 = 3, and Pr.53 = 1.Multi-speed is priorit... More Details >>

    • No:21963
    • Release Date:2018/08/22 16:30
  • I want to synchronize the Z200 and E500.

    If you are using analog voltage commands, connect the voltage inputs to the FR-E500 and FR-Z200 in parallel to equalize inputs to both units and speeds are s... More Details >>

    • No:21929
    • Release Date:2018/08/22 16:30
  • Items controllable via CC-Link

    1. Not all items can be controlled.   - Functions that cannot be controlled JOG, AU, CS, OH, X10, X11, X12, and X16 functions (Other functions can be control... More Details >>

    • No:21459
    • Release Date:2018/08/22 16:27
  • UL standard certification number

    The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>

    • No:21506
    • Release Date:2018/08/22 16:28
  • External wiring for CC-Link operation

    For the combination of the FR-A500 + FR-A5NC, Pr.338 and Pr.339 are used to specify whether the external signals or CC-Link commands are used to set the runn... More Details >>

    • No:21973
    • Release Date:2018/08/22 16:30
  • Countermeasures when input power supply is turned off upon equipment fault

    1. When the inverter power supply is turned OFF, the inverter is disconnected from the CC-Link network. However, since the CC-Link master station has the aut... More Details >>

    • No:21390
    • Release Date:2018/08/22 16:27
  • Speed does not exceed 46 Hz

    Since the inverter displayed "0.00" instead of an error when the inverter speed dropped to 0 Hz and stopped by holding the winding machine by hand, it is con... More Details >>

    • No:21492
    • Release Date:2018/08/22 16:27
  • Overcurrent

    Frequent occurrences of OL means that the inverter is overloaded. Since the inverter can go faulty if it is constantly overloaded, you need to take a counter... More Details >>

    • No:21430
    • Release Date:2018/08/22 16:27
  • Current monitor display

    The current monitor displays the average value of the three-phase current. The three-phase voltage is not incorporated for the voltage monitor. The output vo... More Details >>

    • No:21376
    • Release Date:2018/08/22 16:27
  • CC-Link

    Although you specify the FR-V200 and others as the inverter models, CC-Link is currently supported by the FR-A500 and FR-E500. The FR-V200E does not support ... More Details >>

    • No:21499
    • Release Date:2018/08/22 16:27