  • Notes when inverter capacity is larger than motor capacity

    When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>

    • No:22040
    • Release Date:2018/08/22 16:30
  • Operation command terminal switching

    It rotates in the forward direction while STF is ON.And then, when STR is turned ON and STF is turned OFF, the inverter decelerates down to 0 Hz within the s... More Details >>

    • No:22070
    • Release Date:2018/08/22 16:30
  • Comparison with E500

    The major differences are:- Capacity range- Availability of regenerative brake resistor- Operation of the operation panel- Number of I/O terminals More Details >>

    • No:22056
    • Release Date:2018/08/22 16:30
  • Selection of high-duty brake resistor

    Select the high-duty brake resistor according to the inverter capacity. More Details >>

    • No:21953
    • Release Date:2018/08/22 16:30
  • Alarm output signal when using CC-Link

    The RX7 output signal is the same as the signals for NO, NC, and transfer contact output.You can change the contents of this output signal using Pr.192.Pr.19... More Details >>

    • No:22008
    • Release Date:2018/08/22 16:30
  • Usage

    1. Changing frequency to 0 Hz(1) Set Pr.8 (Deceleration time) to 0 second.If the load is large, the stall prevention function may work to lengthen decelerati... More Details >>

    • No:22019
    • Release Date:2018/08/22 16:30
  • Amount of heat generated

    The amount of heat generated by the FR-E500 series inverter is registered in the Mitsubishi Electric FA Global Website Member's page. Refer to the technical ... More Details >>

    • No:21382
    • Release Date:2018/08/22 16:27
  • Inverter input power supply

    Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>

    • No:22106
    • Release Date:2018/08/22 16:31
  • RS485 communication

    The RS485 communication is explained in the FREQROL-E500 Instruction Manual. This Instruction Manual is published on the member's page of Mitsubishi Electric... More Details >>

    • No:21426
    • Release Date:2018/08/22 16:27
  • Current monitor display

    The current monitor displays the average value of the three-phase current. The three-phase voltage is not incorporated for the voltage monitor. The output vo... More Details >>

    • No:21376
    • Release Date:2018/08/22 16:27