If the MC on the input side is shut off using the fault output of the FR-E500, the inverter's fault records are left in the faults history. More Details >>
- No:22096
- Release Date:2018/08/22 16:30
-
If you are using an external VR, influence by noise is probable.Setting Pr.74 (Input filter time constant) to a higher value stabilizes the frequency command... More Details >>
- No:22061
- Release Date:2018/08/22 16:30
-
Connecting the brake resistor allows for quick deceleration because the regenerative power is processed. (The brake torque increases.)Therefore, when an exte... More Details >>
- No:22045
- Release Date:2018/08/22 16:30
-
Notes when inverter capacity is larger than motor capacity
When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>
- No:22040
- Release Date:2018/08/22 16:30
-
Alarm output signal when using CC-Link
The RX7 output signal is the same as the signals for NO, NC, and transfer contact output.You can change the contents of this output signal using Pr.192.Pr.19... More Details >>
- No:22008
- Release Date:2018/08/22 16:30
-
Take the following countermeasure:1. If the thermal trips in low-speed operation, trips can be avoided, depending on the external thermal relay operation cha... More Details >>
- No:21954
- Release Date:2018/08/22 16:30
-
Connecting operation panel to enclosure
To connect the operation panel to the enclosure, use the parameter unit connection cable FR-CB201, FR-CB203, or FR-CB205. The maximum cable length is 5 m. No... More Details >>
- No:21542
- Release Date:2018/08/22 16:28
-
Parameters not covered in manual are displayed
Pr.168 indicates the inverter software version.Pr.169 indicates the inverter software subversion history. These two parameters are only used by the manufactu... More Details >>
- No:21532
- Release Date:2018/08/22 16:28
-
Since the inverter displayed "0.00" instead of an error when the inverter speed dropped to 0 Hz and stopped by holding the winding machine by hand, it is con... More Details >>
- No:21492
- Release Date:2018/08/22 16:27
-
"Err" is displayed when STF signal turns ON
Possible causes are:1. The reset signal (RES) is ON. 2. The built-in CPU is not working properly due to contact faults of the inverter parts. Check the exte... More Details >>
- No:21484
- Release Date:2018/08/22 16:27