  • Operation at external operation/stop

    It is recommended to turn OFF the start signals (STF and STR) when stopping the inverter.In this case, it is not probable that the motor rotates due to a cal... More Details >>

    • No:22102
    • Release Date:2018/08/22 16:31
  • Output side earth (ground) fault overcurrent protection

    1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>

    • No:21394
    • Release Date:2018/08/22 16:27
  • Instantaneous power failure of facilities

    1. If the start signal is present when the power and communication restore, the inverter starts operation. 2. Similarly to the above, if the start signal is ... More Details >>

    • No:22093
    • Release Date:2018/08/22 16:30
  • Inverter

    You can use the Hioki Memory HiCorder and clamp-on AC/DC high tester.You can observe the inverter's frequency in one of the following two methods:1. Attach t... More Details >>

    • No:22082
    • Release Date:2018/08/22 16:30
  • Inverter outline dimension CAD data

    The outline dimension diagram is found on the member's page of Mitsubishi Electric FA Global Website.Contact our sales personnel for details on the programma... More Details >>

    • No:22053
    • Release Date:2018/08/22 16:30
  • Control method

    1. Can I set the frequency by the external potentiometer when multi-speed signal is 0 (nothing is input)?-> It is possible by using the external operation... More Details >>

    • No:21990
    • Release Date:2018/08/22 16:30
  • Regenerative brake resistor

    The brake resistor is not built in the inverter. Purchase the optional resistor and connect it to the inverter.Inverter only (without resistor)Continuous reg... More Details >>

    • No:21989
    • Release Date:2018/08/22 16:30
  • Installation dimensions

    Refer to the outline dimension. More Details >>

    • No:21513
    • Release Date:2018/08/22 16:28
  • External thermal overheat

    Take the following countermeasure:1. If the thermal trips in low-speed operation, trips can be avoided, depending on the external thermal relay operation cha... More Details >>

    • No:21954
    • Release Date:2018/08/22 16:30
  • I want to shorten deceleration time of small capacity motor

    You can use an inverter with a larger capacity than the motor. You cannot connect a brake resistor to the FR-E520-0.1K and 0.2K. With the FR-E520-0.1K or 0.2... More Details >>

    • No:21463
    • Release Date:2018/08/22 16:27