Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>
- No:22106
- Release Date:2018/08/22 16:31
-
Communication operation with FR-E500
We have no sample program for RS485 communication. Since the communication method of the FR-SW0-SETUP uses a different protocol from 485 communication and st... More Details >>
- No:21451
- Release Date:2018/08/22 16:27
-
Items controllable via CC-Link
1. Not all items can be controlled. - Functions that cannot be controlled JOG, AU, CS, OH, X10, X11, X12, and X16 functions (Other functions can be control... More Details >>
- No:21459
- Release Date:2018/08/22 16:27
-
The internal processing speed is not published. The analog input specifications are as follows: FR-A500???1/4000FR-E500???1/1000MR-H???1/4000 More Details >>
- No:21550
- Release Date:2018/08/22 16:28
-
Operation command terminal switching
It rotates in the forward direction while STF is ON.And then, when STR is turned ON and STF is turned OFF, the inverter decelerates down to 0 Hz within the s... More Details >>
- No:22070
- Release Date:2018/08/22 16:30
-
Refer to the outline dimension. More Details >>
- No:21513
- Release Date:2018/08/22 16:28
-
External wiring for CC-Link operation
For the combination of the FR-A500 + FR-A5NC, Pr.338 and Pr.339 are used to specify whether the external signals or CC-Link commands are used to set the runn... More Details >>
- No:21973
- Release Date:2018/08/22 16:30
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
-
General-purpose magnetic flux vector control is effective at low speed under a heavy load.To shorten the acceleration time, use Pr.44 to set the second accel... More Details >>
- No:22059
- Release Date:2018/08/22 16:30
-
If you are using an external VR, influence by noise is probable.Setting Pr.74 (Input filter time constant) to a higher value stabilizes the frequency command... More Details >>
- No:22061
- Release Date:2018/08/22 16:30