Notes when inverter capacity is larger than motor capacity
When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>
- No:22040
- Release Date:2018/08/22 16:30
-
Using built-in potentiometer and multi-speed together
Yes. Set Pr.79 = 3. (Input the start signal from an external source.) More Details >>
- No:21950
- Release Date:2018/08/22 16:30
-
The inverter uses PWM control to change the output voltage and frequency to vary the motor speed. PWM stands for Pulse Width Modulation. Voltage is chopped i... More Details >>
- No:21549
- Release Date:2018/08/22 16:28
-
The output current monitor of the inverter displays the output current effective value of the three phases measured by the current sensor. It does not displa... More Details >>
- No:21373
- Release Date:2018/08/22 16:27
-
Setting Pr.37 to the machine speed at 60 Hz switches the frequency monitor to the rotations per minute monitor.Note that the speed setting must be input in a... More Details >>
- No:22072
- Release Date:2018/08/22 16:30
-
Be sure to use the FR-E5P to mount the operation panel.This is because the board is bare on the back of the operation panel and a dedicated connector is requ... More Details >>
- No:22030
- Release Date:2018/08/22 16:30
-
If the MC on the input side is shut off using the fault output of the FR-E500, the inverter's fault records are left in the faults history. More Details >>
- No:22096
- Release Date:2018/08/22 16:30
-
Connecting operation panel to enclosure
To connect the operation panel to the enclosure, use the parameter unit connection cable FR-CB201, FR-CB203, or FR-CB205. The maximum cable length is 5 m. No... More Details >>
- No:21542
- Release Date:2018/08/22 16:28
-
Built-in potentiometer and current input switching control
For setting the frequency, you cannot switch between the operation panel potentiometer and current input from an external source.To switch between the extern... More Details >>
- No:21985
- Release Date:2018/08/22 16:30
-
Since a large load is applied to the motor when the electromagnetic clutch turns on, overcurrent may occur if the load is heavy. To ensure that the rated cur... More Details >>
- No:21955
- Release Date:2018/08/22 16:30