Connecting the brake resistor allows for quick deceleration because the regenerative power is processed. (The brake torque increases.)Therefore, when an exte... More Details >>
- No:22045
- Release Date:2018/08/22 16:30
-
Items controllable via CC-Link
1. Not all items can be controlled. - Functions that cannot be controlled JOG, AU, CS, OH, X10, X11, X12, and X16 functions (Other functions can be control... More Details >>
- No:21459
- Release Date:2018/08/22 16:27
-
I want to synchronize the Z200 and E500.
If you are using analog voltage commands, connect the voltage inputs to the FR-E500 and FR-Z200 in parallel to equalize inputs to both units and speeds are s... More Details >>
- No:21929
- Release Date:2018/08/22 16:30
-
Communication operation with FR-E500
We have no sample program for RS485 communication. Since the communication method of the FR-SW0-SETUP uses a different protocol from 485 communication and st... More Details >>
- No:21451
- Release Date:2018/08/22 16:27
-
FR-E520 operation mode (Pr.79) selection
The FR-E500 manufactured before May 1998 behaved as you mentioned, and the potentiometer becomes unavailable once you set the frequency on the operation pane... More Details >>
- No:21525
- Release Date:2018/08/22 16:28
-
Countermeasure against the instantaneous power failure with the inverter
The power cannot be supplied to the control power supply separately for the FR-A024/A044 and small type FR-E500. Therefore, the UPS is not available. More Details >>
- No:21368
- Release Date:2018/08/22 16:27
-
Relationship between frequency and output torque
The output torque characteristics of the FREQROL-E500 series are shown in the figure below. Figure 1 More Details >>
- No:22024
- Release Date:2018/08/22 16:30
-
Automatic overload control of inverter
The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>
- No:21409
- Release Date:2018/08/22 16:27
-
If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>
- No:22052
- Release Date:2018/08/22 16:30
-
Output side earth (ground) fault overcurrent protection
1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>
- No:21394
- Release Date:2018/08/22 16:27