FAQ within [ FREQROL-E500 ]

61-70 of Total 85

prev 7 / 9page next
  • Alarm output signal when using CC-Link

    The RX7 output signal is the same as the signals for NO, NC, and transfer contact output.You can change the contents of this output signal using Pr.192.Pr.19... More Details >>

    • No:22008
    • Release Date:2018/08/22 16:30
  • Noise from motor at low speed

    It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>

    • No:21428
    • Release Date:2018/08/22 16:27
  • Driving 200 V motor by 400 V inverter

    Your suggested use is not recommended due to the following reasons: Output voltage of the 400 V inverter contains "micro surge". Usually this surge voltage i... More Details >>

    • No:21403
    • Release Date:2018/08/22 16:27
  • Inverter input power supply

    Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>

    • No:22106
    • Release Date:2018/08/22 16:31
  • Instantaneous power failure of facilities

    1. If the start signal is present when the power and communication restore, the inverter starts operation. 2. Similarly to the above, if the start signal is ... More Details >>

    • No:22093
    • Release Date:2018/08/22 16:30
  • Operation command terminal switching

    It rotates in the forward direction while STF is ON.And then, when STR is turned ON and STF is turned OFF, the inverter decelerates down to 0 Hz within the s... More Details >>

    • No:22070
    • Release Date:2018/08/22 16:30
  • Connecting operation panel to enclosure

    To connect the operation panel to the enclosure, use the parameter unit connection cable FR-CB201, FR-CB203, or FR-CB205. The maximum cable length is 5 m. No... More Details >>

    • No:21542
    • Release Date:2018/08/22 16:28
  • CC-Link

    Although you specify the FR-V200 and others as the inverter models, CC-Link is currently supported by the FR-A500 and FR-E500. The FR-V200E does not support ... More Details >>

    • No:21499
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Ensure that the inverter is in the PU operation mode and stopped, change the following parameters: 1. Read Pr.923 (Built-in frequency setting potentiometer g... More Details >>

    • No:21416
    • Release Date:2018/08/22 16:27
  • Analog output

    The FM output is 0 to 8 VDC pulse. More Details >>

    • No:22039
    • Release Date:2018/08/22 16:30

61-70 of Total 85