  • Monitor

    The output current monitor of the inverter displays the output current effective value of the three phases measured by the current sensor. It does not displa... More Details >>

    • No:21373
    • Release Date:2018/08/22 16:27
  • Inverter input power supply

    Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>

    • No:22106
    • Release Date:2018/08/22 16:31
  • Operation panel

    Be sure to use the FR-E5P to mount the operation panel.This is because the board is bare on the back of the operation panel and a dedicated connector is requ... More Details >>

    • No:22030
    • Release Date:2018/08/22 16:30
  • Items controllable via CC-Link

    1. Not all items can be controlled.   - Functions that cannot be controlled JOG, AU, CS, OH, X10, X11, X12, and X16 functions (Other functions can be control... More Details >>

    • No:21459
    • Release Date:2018/08/22 16:27
  • Speed 2 operation with potentiometer on operation panel

    Yes. Set parameters as below.For FR-E500Set Pr.79 =3, and Pr.146= 0.Multi-speed is prioritized.For FR-S500Set Pr.79 = 3, and Pr.53 = 1.Multi-speed is priorit... More Details >>

    • No:21963
    • Release Date:2018/08/22 16:30
  • Frequency display deviation

    If you are using an external VR, influence by noise is probable.Setting Pr.74 (Input filter time constant) to a higher value stabilizes the frequency command... More Details >>

    • No:22061
    • Release Date:2018/08/22 16:30
  • Parameter unit display

    Setting Pr.37 to the machine speed at 60 Hz switches the frequency monitor to the rotations per minute monitor.Note that the speed setting must be input in a... More Details >>

    • No:22072
    • Release Date:2018/08/22 16:30
  • Parameters not covered in manual are displayed

    Pr.168 indicates the inverter software version.Pr.169 indicates the inverter software subversion history. These two parameters are only used by the manufactu... More Details >>

    • No:21532
    • Release Date:2018/08/22 16:28
  • Instantaneous power failure of facilities

    1. If the start signal is present when the power and communication restore, the inverter starts operation. 2. Similarly to the above, if the start signal is ... More Details >>

    • No:22093
    • Release Date:2018/08/22 16:30
  • Overcurrent

    Frequent occurrences of OL means that the inverter is overloaded. Since the inverter can go faulty if it is constantly overloaded, you need to take a counter... More Details >>

    • No:21430
    • Release Date:2018/08/22 16:27