- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E500
FAQ
Keyword Search
FAQ within [ FREQROL-E500 ]
-
Operation command terminal switching
It rotates in the forward direction while STF is ON.And then, when STR is turned ON and STF is turned OFF, the inverter decelerates down to 0 Hz within the s... More Details >>
- No:22070
- Release Date:2018/08/22 16:30
-
1. Changing frequency to 0 Hz(1) Set Pr.8 (Deceleration time) to 0 second.If the load is large, the stall prevention function may work to lengthen decelerati... More Details >>
- No:22019
- Release Date:2018/08/22 16:30
-
Using built-in potentiometer and multi-speed together
Yes. Set Pr.79 = 3. (Input the start signal from an external source.) More Details >>
- No:21950
- Release Date:2018/08/22 16:30
-
Communication operation with FR-E500
We have no sample program for RS485 communication. Since the communication method of the FR-SW0-SETUP uses a different protocol from 485 communication and st... More Details >>
- No:21451
- Release Date:2018/08/22 16:27
-
The estimated lives of the parts of the FREQROL-E500 are as follows: Cooling fan at surrounding air temperature of 35 deg C???30,000 hrsPower supply smoothin... More Details >>
- No:22071
- Release Date:2018/08/22 16:30
-
Setting Pr.37 to the machine speed at 60 Hz switches the frequency monitor to the rotations per minute monitor.Note that the speed setting must be input in a... More Details >>
- No:22072
- Release Date:2018/08/22 16:30
-
Notes on using single-phase 200 V
With the single-phase 200 V input specifications, the input cable current increases. Therefore, choose larger power supply capacity and NF/MC than three-phas... More Details >>
- No:21406
- Release Date:2018/08/22 16:27
-
Operation at external operation/stop
It is recommended to turn OFF the start signals (STF and STR) when stopping the inverter.In this case, it is not probable that the motor rotates due to a cal... More Details >>
- No:22102
- Release Date:2018/08/22 16:31
-
"PS" appears when the STOP key on the operation panel is pressed during external operation. It is considered that someone pressed the key. Dismiss "PS" in on... More Details >>
- No:21478
- Release Date:2018/08/22 16:27
-
If the MC on the input side is shut off using the fault output of the FR-E500, the inverter's fault records are left in the faults history. More Details >>
- No:22096
- Release Date:2018/08/22 16:30