The major differences are:- Capacity range- Availability of regenerative brake resistor- Operation of the operation panel- Number of I/O terminals More Details >>
- No:22056
- Release Date:2018/08/22 16:30
-
Take the following countermeasure:1. If the thermal trips in low-speed operation, trips can be avoided, depending on the external thermal relay operation cha... More Details >>
- No:21954
- Release Date:2018/08/22 16:30
-
The RS485 communication is explained in the FREQROL-E500 Instruction Manual. This Instruction Manual is published on the member's page of Mitsubishi Electric... More Details >>
- No:21426
- Release Date:2018/08/22 16:27
-
Driving 200 V motor by 400 V inverter
Your suggested use is not recommended due to the following reasons: Output voltage of the 400 V inverter contains "micro surge". Usually this surge voltage i... More Details >>
- No:21403
- Release Date:2018/08/22 16:27
-
The current monitor displays the average value of the three-phase current. The three-phase voltage is not incorporated for the voltage monitor. The output vo... More Details >>
- No:21376
- Release Date:2018/08/22 16:27
-
Setting Pr.37 to the machine speed at 60 Hz switches the frequency monitor to the rotations per minute monitor.Note that the speed setting must be input in a... More Details >>
- No:22072
- Release Date:2018/08/22 16:30
-
Operation command terminal switching
It rotates in the forward direction while STF is ON.And then, when STR is turned ON and STF is turned OFF, the inverter decelerates down to 0 Hz within the s... More Details >>
- No:22070
- Release Date:2018/08/22 16:30
-
Relationship between frequency and output torque
The output torque characteristics of the FREQROL-E500 series are shown in the figure below. Figure 1 More Details >>
- No:22024
- Release Date:2018/08/22 16:30
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
-
Notes when inverter capacity is larger than motor capacity
When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>
- No:22040
- Release Date:2018/08/22 16:30