FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E500
FAQ
Keyword Search
FAQ within [ FREQROL-E500 ]
-
Speed control failure due to 20 mA from DC 4
It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>
- No:21998
- Release Date:2018/08/22 16:30
-
Surge voltage of 400 V inverter
No. Although the carrier frequency increases or decreases the switching count, the switching speed is the OFF-to-ON speed of the IGBT element of the inverter... More Details >>
- No:21401
- Release Date:2018/08/22 16:27
-
Inverter drive of 400 V class motor
When the wiring between the inverter and motor is long, surge voltage occurs at the terminal of the motor.This surge voltage deteriorates insulation of the m... More Details >>
- No:21926
- Release Date:2018/08/22 16:30
-
Automatic overload control of inverter
The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>
- No:21409
- Release Date:2018/08/22 16:27
-
UL standard certification number
The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>
- No:21506
- Release Date:2018/08/22 16:28
-
The inverter uses PWM control to change the output voltage and frequency to vary the motor speed. PWM stands for Pulse Width Modulation. Voltage is chopped i... More Details >>
- No:21549
- Release Date:2018/08/22 16:28
-
Difference between SU (up to frequency) and FU (frequency detection)
- SU signal (up to frequency signal)This signal is output when the inverter output frequency reaches the set frequency (the frequency the inverter is require... More Details >>
- No:21436
- Release Date:2018/08/22 16:27
-
If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>
- No:22052
- Release Date:2018/08/22 16:30
-
The following causes are probable for persistent Err. display: 1. The terminals RES and SD are always short-circuited. 2. Operation panel contact or operatio... More Details >>
- No:21412
- Release Date:2018/08/22 16:27
-
Output side earth (ground) fault overcurrent protection
1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>
- No:21394
- Release Date:2018/08/22 16:27
71-80 of Total 85