Countermeasure against the instantaneous power failure with the inverter
The power cannot be supplied to the control power supply separately for the FR-A024/A044 and small type FR-E500. Therefore, the UPS is not available. More Details >>
- No:21368
- Release Date:2018/08/22 16:27
-
Err display on operation panel
The following causes are probable for this Err display:- Operation error (for example, you tried to input a value other than the available range of parameter... More Details >>
- No:22063
- Release Date:2018/08/22 16:30
-
UL standard certification number
The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>
- No:21506
- Release Date:2018/08/22 16:28
-
If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>
- No:22052
- Release Date:2018/08/22 16:30
-
Using the inverter's input terminal, you can use up to 15 speeds.This function is supported by the current 500 series products (A500, F500, E500, and S500).U... More Details >>
- No:21947
- Release Date:2018/08/22 16:30
-
Automatic overload control of inverter
The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>
- No:21409
- Release Date:2018/08/22 16:27
-
Output side earth (ground) fault overcurrent protection
1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>
- No:21394
- Release Date:2018/08/22 16:27
-
Speed control failure due to 20 mA from DC 4
It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>
- No:21998
- Release Date:2018/08/22 16:30
-
Power factor improving effect by option
Installing the high power factor converter brings the power factor improving effect of 99% or higher.Therefore, when the high power factor converter is used,... More Details >>
- No:22020
- Release Date:2018/08/22 16:30
-
When the wire between the 400 V inverter and motor is long (20 m or longer), surge voltage occurs momentarily. This voltage is as two or more times as the DC... More Details >>
- No:21404
- Release Date:2018/08/22 16:27