  • Surge voltage of 400 V motor

    When the wire between the 400 V inverter and motor is long (20 m or longer), surge voltage occurs momentarily. This voltage is as two or more times as the DC... More Details >>

    • No:21404
    • Release Date:2018/08/22 16:27
  • Dealing with Err.

    The following causes are probable for persistent Err. display: 1. The terminals RES and SD are always short-circuited. 2. Operation panel contact or operatio... More Details >>

    • No:21412
    • Release Date:2018/08/22 16:27
  • Alarm output signal when using CC-Link

    The RX7 output signal is the same as the signals for NO, NC, and transfer contact output.You can change the contents of this output signal using Pr.192.Pr.19... More Details >>

    • No:22008
    • Release Date:2018/08/22 16:30
  • Inverter drive of 400 V class motor

    When the wiring between the inverter and motor is long, surge voltage occurs at the terminal of the motor.This surge voltage deteriorates insulation of the m... More Details >>

    • No:21926
    • Release Date:2018/08/22 16:30
  • Automatic overload control of inverter

    The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>

    • No:21409
    • Release Date:2018/08/22 16:27
  • Speed change due to power supply voltage fluctuation

    1. The output frequency satisfies the "control specification/frequency precision" even when the power supply voltage changes, but the output voltage cannot r... More Details >>

    • No:22069
    • Release Date:2018/08/22 16:30
  • UL standard certification number

    The UL standard certification numbers (UL Listing Card No.) of the FR-E500, FR-A500, and FR-A200 are as follows: FR-A200 series??????E131592FR-A500 series???... More Details >>

    • No:21506
    • Release Date:2018/08/22 16:28
  • Parameter setting

    1. Pr.146 is not available.   Some catalogs and manuals cover this parameter, but it is an error.   The latest catalogs and manuals have been corrected to el... More Details >>

    • No:21529
    • Release Date:2018/08/22 16:28
  • Difference between SU (up to frequency) and FU (frequency detection)

    - SU signal (up to frequency signal)This signal is output when the inverter output frequency reaches the set frequency (the frequency the inverter is require... More Details >>

    • No:21436
    • Release Date:2018/08/22 16:27
  • Output phase loss alarm

    If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>

    • No:22052
    • Release Date:2018/08/22 16:30