  • Overcurrent

    Frequent occurrences of OL means that the inverter is overloaded. Since the inverter can go faulty if it is constantly overloaded, you need to take a counter... More Details >>

    • No:21430
    • Release Date:2018/08/22 16:27
  • Speed change due to power supply voltage fluctuation

    1. The output frequency satisfies the "control specification/frequency precision" even when the power supply voltage changes, but the output voltage cannot r... More Details >>

    • No:22069
    • Release Date:2018/08/22 16:30
  • Automatic overload control of inverter

    The inverter has the current limit function. This automatically controls the frequency so that the preset current value may not be exceeded. (Note that the m... More Details >>

    • No:21409
    • Release Date:2018/08/22 16:27
  • "Err" is displayed when STF signal turns ON

    Possible causes are:1. The reset signal (RES) is ON. 2. The built-in CPU is not working properly due to contact faults of the inverter parts. Check the exte... More Details >>

    • No:21484
    • Release Date:2018/08/22 16:27
  • Speed control failure due to 20 mA from DC 4

    It seems that there is a read error for 20 mA DC inside the inverter.Setting Pr.905 to 50 Hz while 20 mA DC is actually flowing between the terminals 4 and 5... More Details >>

    • No:21998
    • Release Date:2018/08/22 16:30
  • Power factor improving effect by option

    Installing the high power factor converter brings the power factor improving effect of 99% or higher.Therefore, when the high power factor converter is used,... More Details >>

    • No:22020
    • Release Date:2018/08/22 16:30
  • Output phase loss alarm

    If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>

    • No:22052
    • Release Date:2018/08/22 16:30
  • What happens if reset occurs during operation?

    This is because when the inverter restarts while the motor is coasting, an overcurrent trip can occur during the restart process. However, the recent types o... More Details >>

    • No:21477
    • Release Date:2018/08/22 16:27
  • Inverter drive of 400 V class motor

    When the wiring between the inverter and motor is long, surge voltage occurs at the terminal of the motor.This surge voltage deteriorates insulation of the m... More Details >>

    • No:21926
    • Release Date:2018/08/22 16:30
  • Surge voltage of 400 V motor

    When the wire between the 400 V inverter and motor is long (20 m or longer), surge voltage occurs momentarily. This voltage is as two or more times as the DC... More Details >>

    • No:21404
    • Release Date:2018/08/22 16:27