  • What happens if reset occurs during operation?

    This is because when the inverter restarts while the motor is coasting, an overcurrent trip can occur during the restart process. However, the recent types o... More Details >>

    • No:21477
    • Release Date:2018/08/22 16:27
  • Inverter drive of 400 V class motor

    When the wiring between the inverter and motor is long, surge voltage occurs at the terminal of the motor.This surge voltage deteriorates insulation of the m... More Details >>

    • No:21926
    • Release Date:2018/08/22 16:30
  • Output side earth (ground) fault overcurrent protection

    1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>

    • No:21394
    • Release Date:2018/08/22 16:27
  • Deceleration overvoltage (E.OV3)

    While the FREQROL-Z200 series and A500 series have a brake resistor built in the capacity up to 7.5K, the FREQROL-E500 series does not have a built-in brake ... More Details >>

    • No:21993
    • Release Date:2018/08/22 16:30
  • Error E.LF

    Measure the megger values on the inverter's output side.If there is no problem:If the motor capacity is extremely smaller than the inverter capacity (as a gu... More Details >>

    • No:21933
    • Release Date:2018/08/22 16:30