  • Connecting potentiometer

    Connect the external potentiometer to the terminals 10, 2, and 5 of the first inverter (be sure to connect the variable terminal to the terminal 2). Connect ... More Details >>

    • No:21462
    • Release Date:2018/08/22 16:27
  • Motor wiring length

    Up to 50 m. Be sure to connect the encoder cables in parallel and use the thicker cable gauge. You can extend this distance up to 100 m by using the long dis... More Details >>

    • No:21641
    • Release Date:2018/08/22 16:28
  • Auto tuning

    Vector control performs high-accuracy calculation using the motor constant. Therefore, to perform vector control operation, the inverter must recognize the m... More Details >>

    • No:21663
    • Release Date:2018/08/22 16:28
  • Encoder signal output

    It can be output by attaching the plug-in option FR-VPA, FR-VPB, or FR-VPC. Note that the output format depends on the option type. FR-VPA: Open collector ou... More Details >>

    • No:21643
    • Release Date:2018/08/22 16:28
  • Torque control accuracy

    Since the torque control accuracy is influenced by change of motor temperature:- Standard product???±5% (at 75 deg C) ±0.5%/deg C of rated torque- Combinatio... More Details >>

    • No:21645
    • Release Date:2018/08/22 16:28
  • Applicable motors

    In addition to the dedicated motor (SF-VR series), the SF-JR series motor with an encoder can be used. You can also use a standard motor by combining it with... More Details >>

    • No:21653
    • Release Date:2018/08/22 16:28
  • Reusing parameter units

    You cannot reuse the parameter unit (FR-PU01) for the FREQROL-Z series, the parameter unit (FR-PU02) for the FREQROL-A200 and A100 series, and the parameter ... More Details >>

    • No:21654
    • Release Date:2018/08/22 16:28
  • Inverter current characteristics

    In general, relationship between T (torque), K (constant), V (voltage), I (current), and F (frequency) is expressed as "T = K × (V/F) × I". Since (V/F) is co... More Details >>

    • No:21505
    • Release Date:2018/08/22 16:28
  • Difference from general-purpose inverter

    While the inverter uses open-loop (V/F) control, it uses semi-closed loop vector control (constant current control). This enables output of stable torque esp... More Details >>

    • No:21659
    • Release Date:2018/08/22 16:28
  • Speed fluctuation ratio

    1. Speed fluctuation ratio when using the FR-V200 + dedicated motor (with an encoder) The vector inverter FR-V200 detects speed by the encoder and speed fluc... More Details >>

    • No:21489
    • Release Date:2018/08/22 16:27