It is not possible to extend the length of the extension cable to over 65cm. Place the main unit separately by using the parallel link or N:N Network functio... More Details >>
- No:24941
- Release Date:2019/04/18 14:25
-
Battery consumption while the programmable controller is powered on
A battery is consumed regardless of the on/off state ofthe programmable controller. Refer to the User's Manual (Hardware Edition) for the module used, and r... More Details >>
- No:24687
- Release Date:2019/02/22 11:44
- Update:2019/02/22 15:22
-
Accessories of the FX3UC-16MR/DS-T and the FX3UC-16MR/D-T
The "FX2NC-100MPCB" power supply cable for main unit is provided with the FX3UC-16MR/DS-T. The "FX2NC-100MPCB" and the "FX2NC-100BPCB" power supply cable for... More Details >>
- No:25005
- Release Date:2019/04/23 11:11
-
File format that can be saved to a CF card in the FX3U-CF-ADP
CSV file can be saved. More Details >>
- No:24938
- Release Date:2019/04/18 14:24
-
Number of files that can be created inside a CF card in the FX3U-CF-ADP
Up to 63 files can be handled simultaneously. In addition, up to 1000 files can be created by creating FIFO function files. * The total capacity of the files... More Details >>
- No:24944
- Release Date:2019/04/18 14:26
-
Model name of a built-in battery (FX3U/FX3UC)
FX3U-32BL More Details >>
- No:22278
- Release Date:2018/08/30 13:48
-
Periodic replacement is recommended. For example, standard life of FX3U-32BL is 5 years (at ambient temperature of 25). The life of the battery changes wit... More Details >>
- No:22262
- Release Date:2018/08/30 13:48
-
Necessity of a battery when a memory cassette is used
A battery is not required when a memory cassette is used. This is because the sequence programsstored in the memory cassette, exceptfor RAM memory cassette, ... More Details >>
- No:24770
- Release Date:2019/02/27 15:00
-
Battery replacement during power-on
Replacethe battery when the programmable controller is powered off. For example, forthe FX3U/FX3UC series, data will be held for about 20 seconds after be... More Details >>
- No:22257
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:54
-
Repair term for the FX programmable controllers after discontinuation of production
Mitsubishi Electric shall accept product repairs for seven years after production of the product is discontinued. However, some products cannot be repaired d... More Details >>