Set "[Pr.45] Home position address" of the basic parameters for home position return • Axis 1 to 16: 72+150n, 73+150n • Axis 17 to 32: 1000072+150n, 1000073+... More Details >>
-
Yes. You can check the servo status through the following monitor data. • "[Md.108] Servo status 1" • "[Md.119] Servo status 2" • "[Md.125] Servo status 3... More Details >>
-
The following shows the initialization procedure. (1) Turn OFF the PLC ready flag. (2) Turn ON "[Cd.2] Parameter initialization request". Set "1" to the buff... More Details >>
-
Error 093EH (SSCNET communication error) occurs when erroneous data is received from servo amplifier. [When the servo parameter "[PA14] Rotation direction s... More Details >>
-
Torque is limited by the lower set value of "[Pr.17] Torque limit setting value" and "[Cd.22] New torque value/forward new torque value".When the current tor... More Details >>
-
Warning 093CH (Home position return data incorrect) occurs when the backup data for absolute position restoration is lost.Execute the machine home position r... More Details >>
-
Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>
-
Error 2035 (Command frequency error) occurs when the servo amplifier detects a command frequency error. (1) When the command from the controller is the permi... More Details >>
-
The following shows the procedure for changing the current value to a new value.(1) Write the new current value to "[Cd. 9] New current value".(2) Write "900... More Details >>
-
Yes. (1) Absolute system (a) When the software stroke limit is invalid Positioning is carried out in a designated direction by "[Cd.40] ABS direction in deg... More Details >>