FAQ


FAQAbout Products

FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Buffer memory addresses of CC-Link modules
If the remote net Ver.1 mode is used, each station number is given fixed buffer memory addresses.If the remote net Ver.2 mode is used, different buffer memor... More Details >>
- No:22992
- Release Date:2018/09/03 17:31
- Category: Network related products
-
RS-485 connection between QJ71C24N and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:22986
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Difference between AJ65SBTB1-32DT and AJ65SBTB1-32DT2
Major differences are shown below. - AJ65SBTB1-32DT- Leakage current at OFF 0.25 mA or lower- Protection function (overload protection, overvoltage protectio... More Details >>
- No:22985
- Release Date:2018/09/03 17:31
- Category: Network related products
-
How refresh devices for CC-Link remote inputs and outputs are assigned
The refresh device setting of the CC-Link parameter assigns any devices to the I/O numbers greater than those assigned to the modules on the same base unit. ... More Details >>
- No:22968
- Release Date:2018/09/03 17:31
- Category: Network related products
-
The cross reference window is not displayed.
Select [View]-> [Cross reference window] from the menu in GX Developer to display the cross reference window. More Details >>
- No:22951
- Release Date:2018/09/03 17:30
- Update:2018/09/25 11:54
- Category: Engineering Software
-
MX Component Version 4's compatibility with the L series CPU
MX Component Version 4 supports the L series CPU. More Details >>
- No:22867
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Compatibility between MX Component Version 3 and 4
Applications created using MX Component Version 3 can be used, as they are, on a personal computer on which MX Component Version 4 is installed. MX Component... More Details >>
- No:22839
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors.(1) The module that has been specified by a FROM/TO instr... More Details >>
- No:22830
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
The error code "2401" is "FILE SET ERROR". The individual information parameter number "1100H" corresponds to a file register. The cause of the error is that... More Details >>
- No:22797
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
How to use LCPU connector terminals
The LCPU connector terminals can be used as terminals for built-in I/O function. The setting of the built-in I/O function can be configured with the paramete... More Details >>
- No:22796
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
861-870 of Total 1110