Regardng compatability with other product series
Although the connection with FX2N series I/O modules, FX2 series intelligent function modules, and FX3 series special adater is not possible, FX3 series inte... More Details >>
- No:22309
- Release Date:2018/08/30 13:55
- Update:2022/12/22 09:46
- Category: MELSEC iQ-F Series , CPU Module , I/O Module
-
The following shows the devices for the battery errors. • [SM51] Battery low latch Turn ON when the voltage of battery reduces to less than 2.5[V]. Remains O... More Details >>
-
Error 3012 occurs when the multiple CPU setting of PLC CPU (CPU No.1) does not match that of Motion CPU. (1) Check if the multiple CPU setting of the Multipl... More Details >>
-
GX Works2 update installation procedure
Download the file directly under the C: drive and then install it. More Details >>
- No:22524
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:28
- Category: MELSEC-Q Series
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Checking the amount of free space of the memory in GX Developer/GX Works2
Select [Tool] -> [Confirm Memory Size] to check the amount. More Details >>
- No:22851
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Regarding simulation function using GX Works3
For FX5U/FX5UC CPU modules, GX Works3 Ver. 1.025B or later is supported, and for FX5UJ CPU modules, GX Works3 Ver. 1.065T or later is supported. FX5S CPU mo... More Details >>
- No:22327
- Release Date:2018/08/30 13:55
- Update:2023/02/15 12:56
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding how to check the date of manufacture
You can check the LOT. on the front of the controller or the nameplate on the right side. Verifying on the front of the Controller Nameplate verification... More Details >>
- No:44968
- Release Date:2025/05/08 09:05
- Category: MELSEC MX Controller MX-F Model
-
Set "[PA04] Function selection A-1" to "_1_ _h: Invalid".(Note): When using Q17nCPUN, set "Servo amplifier parameter 23 (Optional function 1)"... More Details >>
-
Inputting device comments in GX Works2
Select [Tool] -> [Options] -> [Program Editor] -> "Ladder/SFC"-> "Comment" and change "Reference/Reflection Target for Device Comment" from "Glob... More Details >>
- No:22559
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series