FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
I/O assignment for additional modules connected to LCPU
In L02CPU(-P), the start I/O number of the additional module begins from 10H. In L26CPU-(P)BT, the number begins from 30H. More Details >>
- No:22808
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors.(1) The module that has been specified by a FROM/TO instr... More Details >>
- No:22830
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Operation performed when file registers are read
Checking "Device Memory" does not read file registers. Switch the Target Memory for "PLC Data" to "Standard RAM" and check "File Register" in the Read from P... More Details >>
- No:22835
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Compatibility between the Japanese and English versions of GX Developer
All the components other than comments in Japanese are supported. Ladder programs and parameters can be used as they are, whether or not they are created usi... More Details >>
- No:22848
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
MX Component Version 4's compatibility with Visual Studio 2008
Yes. More Details >>
- No:22879
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Limit on the display of data collected in GX LogViewer to 32 values
GX LogViewer is made to a specification that allows a single trend window to display a maximum of 32 graphs. When there are more than 32 logging data values,... More Details >>
- No:22889
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
The number of CC-Link modules mountable with a universal model QCPU module
If the parameter is set, the following number of modules can be mounted at maximum. - Q00UJ/Q00U/Q01UCPU: Up to 2 modules - Q02UCPU: Up to 4 modules - Uni... More Details >>
- No:22981
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:20
- Category: Network related products
-
Detecting the number of disconnections when using QJ71E71-100
The number of disconnections detected can be checked by reading the buffer memory address 5203H (Disconnection detection count). Disconnections are detected ... More Details >>
- No:23003
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:49
- Category: Network related products
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Data length for fixed buffer data communications by QJ71E71
The units of send data and receive data are shown below. - Fixed buffer data communications with the "Procedure Exist" control method: Words - Fixed buff... More Details >>
- No:23061
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:17
- Category: Network related products
361-370 of Total 1123