Regarding setting the FX5 CPU Module that does not support the simple CPU communication function
When connecting 2 FX5 CPU Modules (firmware version 1.110 or later) that support the Simple CPU communication function and 2 FX5 CPU Modules (firmware vers... More Details >>
- No:44329
- Release Date:2024/03/20 13:35
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the differences between Latches (1) and (2)
Whether the latch range is set by default is different. ・Latch (1) — Latch range is set by default. This can be changed at any time. ・Latch (2) — No latch ... More Details >>
- No:39351
- Release Date:2023/02/15 13:08
- Update:2024/08/19 09:54
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding the number of expansion adapters and expansion board connections for FX5S CPU module
Up to 6 devices can be connected. Extension adapters/boards (Max. 2 units) + analog extension adapters (Max. 4 units). *Using an SD memory card module ... More Details >>
- No:39336
- Release Date:2023/02/14 17:13
- Category: MELSEC iQ-F Series , CPU Module
-
Check if 24 VDC power is supplied to "1A7" (pin No.) of the external input signal connector. More Details >>
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
CC-Link IE field When a network such as Network Basic is interrupted, the CPU module does not stop and continues to run. When the CC-Link IE Field Network i... More Details >>
- No:44611
- Release Date:2024/11/28 16:11
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
It cannot. Because there will be two CC-link IE field network Basic master stations in a network. More Details >>
- No:39346
- Release Date:2023/02/15 10:05
- Update:2024/04/25 10:10
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
The following shows the devices for the battery errors. • [SM51] Battery low latch Turn ON when the voltage of battery reduces to less than 2.5[V]. Remains O... More Details >>
-
Regarding CC-Link settings using GX Works3
Parameters can be set when connecting the MELSEC iQ-F series with FX5-CCL-MS(CC-Link system master/intelligent device). However, when connecting with FX3U-1... More Details >>
- No:22317
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:19
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software , Network/Communication
-
How to wire the 24V DC power supply for sensors
Connect the "0V (-)" terminal of the external 24V DC power supply to the "COM" terminal (- side of the built-in power supply), one of the input terminals of ... More Details >>