FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Maximum number of characters in a comment that can be transferred to a FX3U series
As project data, up to 32 one-byte characters (16 two-byte characters) can be input to each global device comment. However, the maximum number of characters ... More Details >>
- No:24700
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Using a specified bit (on/off) of a word device (D) as a condition for a contact
In the FX3U/FX3UC series, a bit in a word device can be specified. It can be specified by "Word device (D only) + Decimal point + Bit position (0 to F)". A... More Details >>
- No:22261
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
M8029 (Instruction execution complete flag) is shared with multiple instructions. To obtain an execution completion result of a specific instruction, insert... More Details >>
- No:24775
- Release Date:2019/02/27 15:34
- Category: MELSEC-F Series , Network related products , Main Unit
-
Regarding the Certificate of non-applicability to export to other countries
For issuance of a certificate, please consult your local Mitsubishi representative. More Details >>
- No:22301
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:15
- Category: MELSEC iQ-F Series , Option , CPU Module , I/O Module , Engineering Software , Network/Communication , Motion/Positioning , High-Speed Counter , Analog
-
Regarding EtherCAT Communications
The FX5 CPU module does not support EtherCAT communication. There are no products in the FX series or iQ-F series that support EtherCAT communication. More Details >>
- No:39313
- Release Date:2023/02/14 08:54
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
The LCPU error code 4116 is displayed when a built-in I/O instruction that is disabled in the parameter setting is executed. Check for the parameter settings... More Details >>
- No:22807
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Regarding how to Monitor Buffer Memory Values
You can monitor buffer memory values in the Ladder Editor by setting in GX Works3 >Tools >Options > Monitor > Common Item > Monitor Buffer Mem... More Details >>
- No:39324
- Release Date:2023/01/12 16:56
- Category: MELSEC iQ-F Series , CPU Module
-
M384 to M1535 and D128 to D1099 can be latched. M1536 to M7679, D1100 to D7999, and R0 to R23999 can be used as latch areas by installing an optional batt... More Details >>
- No:24703
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
When the message "An unusable COM port was specified" is displayed
RS-232 is selected as PC side I/F in Transfer Setup of GX Developer or GX Works2.Change the setting in PC side I/F to USB. More Details >>
- No:22517
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
-
File export of ladder programs
(1) If only GX Developer is used - The operation cannot be carried out for ladder programs. - For device comments, copy and paste operations can be carri... More Details >>
- No:22840
- Release Date:2018/09/03 17:30
- Update:2018/09/22 13:22
- Category: Engineering Software
991-1000 of Total 1023