Ethernet system configuration of a redundant system
The following figure shows the basic configuration. When a control system Ethernet module is faulty or disconnected, the system is switched at a disco... More Details >>
- No:22718
- Release Date:2018/09/03 17:29
- Update:2018/09/18 11:45
- Category: MELSEC-Q Series
-
The heater disconnection detection function monitors the heater current on the transistor output. If no current flows when the transistor is ON, it is consi... More Details >>
- No:22773
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:58
- Category: MELSEC-L Series
-
CSV file storage timing in L series logging function
No. More Details >>
- No:22793
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
- Ambient temperature: 25+/-5degrees Celsius with tolerance of +/-0.1% - Ambient temperature: 0 to 55degrees Celsius with tolerance of +/-0.2% (Accuracy f... More Details >>
- No:22811
- Release Date:2018/09/03 17:30
- Update:2018/09/26 16:46
- Category: MELSEC-L Series
-
GX Works2's compatibility with the ACPU modules
GX Works2 does not support the ACPU modules.Use GX Developer for the ACPU modules.GX Developer is included on the CD-ROM of GX Works2.For the installation pr... More Details >>
- No:22873
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Compatibility of the high speed data logger module's report function with 64-bit Excel2010
The high speed data logger module's report function does not support 64-bit Excel2010. More Details >>
- No:22897
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
RS-485 connection between QJ71C24N and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:22986
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Using a FROM/TO instruction after AJ71UC24 is replaced with QJ71C24N
I/O signals and buffer memory addresses need to be changed but data communications can be conducted using a FROM/TO instruction and X/Y signals. More Details >>
- No:23017
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Replacement of the fuse in the FX programmable controller
Customers cannot replace the fuse. For the replacement, please consult your local Mitsubishi representative. More Details >>
- No:24909
- Release Date:2019/04/15 11:30
- Category: MELSEC-F Series , Main Unit
-
Target address change during the positioning operation in the FX3U-1PG
Yes, it is possible. Set a new value for the target address to the target address change value (BFM#54, #53) during the positioning operation. * The targ... More Details >>
- No:24986
- Release Date:2019/04/23 07:22
- Category: MELSEC-F Series , Positioning Control