FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Heat generation of Q61P power supply module
Since the conversion efficiency of the power supply module is approximately 70%, and 30% of the output power is dissipated as heat, the power consumption is ... More Details >>
- No:22529
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
-
No. More Details >>
- No:22589
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:42
- Category: MELSEC-Q Series
-
Print settings of the device list in GX Works2
When [Display Option] -> [Used devices] -> [Contact] and [Coil] are selected in the Device List window, devices used are not displayed. More Details >>
- No:22661
- Release Date:2018/09/03 17:29
- Update:2018/09/21 12:18
- Category: MELSEC-Q Series
-
How to check the capacity of the file registers in use
The capacity file registers currently have can be checked in the file register setting section ([PLC Parameter] -> [PLC File] tab). More Details >>
- No:22694
- Release Date:2018/09/03 17:29
- Update:2018/09/21 14:19
- Category: MELSEC-Q Series
-
Pulse width with which the QX42 recognizes all pulses
Maximum scan time (10 ms) + Response time (10 ms) = Pulse width with which the module recognizes all pulses (20 ms) More Details >>
- No:22720
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
The contents of the standard RAM and latch devices are not erased if the battery replacement is completed within three minutes, which is the backup power tim... More Details >>
- No:22733
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Communication data code of the MC protocol for the built-in Ethernet port in LCPU
The communication data code is selectable by the communication data code setting in [Parameter] -> [PLC Parameter] -> [Built-in Ethernet Port Setting]. More Details >>
- No:22735
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:22
- Category: MELSEC-L Series
-
Maximum number of connectable modules to LCPU when it is not extended
Up to 10 modules can be connected in the system as a whole except for the power supply module, CPU module, display unit, RS232C adapter, and END cover. Some ... More Details >>
- No:22775
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Causes to why SD1286 does not turn on during socket communication of LCPU
Check the following. - Whether the external device specifies the port number of the corresponding connection to the L series CPU. - In the TCP fixed-length... More Details >>
- No:22787
- Release Date:2018/09/03 17:30
- Update:2018/09/22 11:51
- Category: MELSEC-L Series
-
How to obtain connectors used for L series connector type I/O modules
A connector is not included. The connector is obtained by user. A6CON1 (soldering connector, straight out type), A6CON2 (crimp connector, straight out type),... More Details >>
- No:22791
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
141-150 of Total 1023