Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Using devices assigned as local labels in another program (GX Works2)
No.To read from another program, assign the devices as global labels. More Details >>
- No:22863
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Opening function block and Structured Text projects in GX Works2
The project can be read by selecting "Open other project" in GX Works2. - Function names for the GX Developer's Structured Text are different from those of ... More Details >>
- No:22864
- Release Date:2018/09/03 17:30
- Update:2018/09/22 14:28
- Category: Engineering Software
-
Local device comments can be read if the comment file in which the local device comments are stored is written to the CPU module. More Details >>
- No:22869
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Switch settings of intelligent function module and I/O assignment settings (GX Works2)
Those switch settings are connected with each other. The switch setting of intelligent function module settings are easier to set. More Details >>
- No:22883
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Writing LJ71C24 modules' parameters using GX Works2
The switch setting is written when CPU module's parameters are written. The settings of "Various Control Specifications" are written when intelligent functio... More Details >>
- No:22912
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Terminating resistors for RS-422 communication of QJ71C24N
The resistance value is 330 ohm, 1/4 W. More Details >>
- No:22965
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:33
- Category: Network related products
-
How refresh devices for CC-Link remote inputs and outputs are assigned
The refresh device setting of the CC-Link parameter assigns any devices to the I/O numbers greater than those assigned to the modules on the same base unit. ... More Details >>
- No:22968
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Link register assignments in MELSECNET/10 networks
For any type of MELSECNET network (II, /10, and H), B and W devices with the same number cannot be used for multiple stations as write areas. Following th... More Details >>
- No:22971
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:24
- Category: Network related products
-
The number of CC-Link modules mountable with a universal model QCPU module
If the parameter is set, the following number of modules can be mounted at maximum. - Q00UJ/Q00U/Q01UCPU: Up to 2 modules - Q02UCPU: Up to 4 modules - Uni... More Details >>
- No:22981
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:20
- Category: Network related products
-
Ethernet cables for the CC-Link IE Field Network
General-purpose Ethernet cables that meet the 1000BASE-T standard (category 5e or higher) can be used. We recommend double shielded cables. Recommended pro... More Details >>
- No:22989
- Release Date:2018/09/03 17:31
- Update:2019/06/27 15:47
- Category: Network related products