FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Regarding the method to check the scan time
The current value of the scan time is stored in the following special devices. Please monitor using GX Works3. ◇Scan information SD520 Current scan time (... More Details >>
- No:22289
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:20
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
How to wire the 24V DC power supply for sensors
Connect the "0V (-)" terminal of the external 24V DC power supply to the "COM" terminal (- side of the built-in power supply), one of the input terminals of ... More Details >>
- No:22281
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit
-
Regarding differences between 8 bit and 16 bit modes for non-protocol communication
In 8-bit mode, the upper 8 bits of transmitted and received data are ignored and only the lower 8 bits are valid data. In 16 bit mode, send/receive data i... More Details >>
- No:39363
- Release Date:2023/02/15 13:04
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding converting FBD/LD Projects
It can't be converted. More Details >>
- No:39328
- Release Date:2023/02/14 09:05
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding EtherNet/IP Communications
The built-in Ethernet port on the FX5 CPU module does not support EtherNet/IP communication. Use FX5-ENET/IP. More Details >>
- No:39319
- Release Date:2023/02/14 08:57
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Input numbers of the FX programmable controllers
Since they are octal, the number after X7 is X10 and after X77 is X100. More Details >>
- No:25000
- Release Date:2019/04/23 10:39
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
File format that can be saved to a CF card in the FX3U-CF-ADP
CSV file can be saved. More Details >>
- No:24938
- Release Date:2019/04/18 14:24
- Category: MELSEC-F Series , Main Unit , Accessories
-
Assignment of remote input device and remote output device of FX3U-16CCL-M
The remote input device and the remote output device cannot be assigned in network parameters. To assign them, create a program for updating data. For de... More Details >>
- No:24792
- Release Date:2019/02/28 09:08
- Category: MELSEC-F Series , Engineering Software , Network/Communication
-
Distinguishing the usage of standard counters and high-speed counters
Standard counters offer counting up to 10Hz. For high-speed input signals which exceed 10Hz, use high-speed counters,interruption function, or another proce... More Details >>
- No:24785
- Release Date:2019/02/27 16:31
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
For output terminals of a programmable controller, one common terminal is used for 1, 2, 4, or 8 output points. Each common line is assigned with a different... More Details >>
- No:24780
- Release Date:2019/02/27 15:58
- Category: MELSEC-F Series , Main Unit
221-230 of Total 1023