Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Using Q series terminal blocks and connectors with MELSEC iQ-R series modules
You can use a Q series 18-point screw terminal block with a MELSEC iQ-R series terminal block type I/O module or analog module. For a 40-pin connector type ... More Details >>
- No:22474
- Release Date:2018/09/03 17:28
- Update:2018/09/19 14:37
- Category: MELSEC iQ-R Series
-
Built-in Ethernet function setting window of MELSEC iQ-R series CPU modules
"Module Parameter" of the CPU module is the setting window. <Setting a built-in Ethernet port> [Navigation Window]-> [Parameter]-> [CPU Modul... More Details >>
- No:22488
- Release Date:2018/09/03 17:28
- Update:2018/09/20 09:40
- Category: MELSEC iQ-R Series
-
You can synchronize the fixed scan communication cycle of the multiple CPU system function with the inter-module synchronization cycle of the inter-module s... More Details >>
- No:22494
- Release Date:2018/09/03 17:28
- Update:2018/09/20 11:12
- Category: MELSEC iQ-R Series
-
CPU modules that support the File Register Extended Setting
The universal model QCPU modules other than Q00UJCPU support the File Register Extended Setting. More Details >>
- No:22627
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
How to suppress the instability of digital-converted output values
(1) Use separate cables for the AC control circuit and the external input signals of an analog input module to avoid the influence of the AC side surges an... More Details >>
- No:22709
- Release Date:2018/09/03 17:29
- Update:2018/09/21 15:11
- Category: MELSEC-Q Series
-
Use of a commercial SD memory card in L series logging function
Yes. Recommended products are listed in the technical bulletin FA-A-0078. More Details >>
- No:22753
- Release Date:2018/09/03 17:29
- Update:2018/10/03 16:25
- Category: MELSEC-L Series
-
The error code "2110" is "SP.UNIT ERROR.". This error may be caused by one of the following factors.(1) The module that has been specified by a FROM/TO instr... More Details >>
- No:22830
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Multiplication in the Structured Text
Basic arithmetic operations cannot be performed on unsigned words. Please assign the multiplier to a signed (single/double) word. More Details >>
- No:22886
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Index modification in function blocks
Index modification cannot be used for labels. To set index modification, use actual devices as the target devices. More Details >>
- No:22930
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Use a T-branch repeater module instead of a terminal block. More Details >>