FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Connecting special adapters to FX3U series
Anexpansion board is required. (However, it is not required when connecting only the special high-speed I/O adapter.) More Details >>
- No:24934
- Release Date:2019/04/18 14:23
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
Setting day of the week when using the TWR instruction (FX3 series)
Day of week is automatically set. When data written to the data register for storing day-of-the-week data is within the setting range (K = 0 to 6), the day ... More Details >>
- No:24777
- Release Date:2019/02/27 15:57
- Category: MELSEC-F Series , Main Unit
-
To assure 32-bit data, "Network Range Assignment" of the control station must satisfy the following conditions.(1) The start device No. of LB is a multiple o... More Details >>
- No:23052
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Difference between CC-Link reserved stations and invalid stations
- Reserved station Reserved stations are not actually connected to the network (but will be connected in the future) but do not appear as data link error... More Details >>
- No:22993
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:37
- Category: Network related products
-
Necessity of terminating resistors in CC-Link communication
No, it is unnecessary. Terminating resistors are only required at both ends of the network. More Details >>
- No:22966
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Checking the amount of free space of the memory in GX Developer/GX Works2
Select [Tool] -> [Confirm Memory Size] to check the amount. More Details >>
- No:22851
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
SD1284 of LCPU with built-in Ethernet port
The bits 0 to F of the special register SD1284 (Open request signal) correspond to the connection numbers 1 to 16. When the open request is sent, the corresp... More Details >>
- No:22784
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
FNC connector pin layout in L series I/O module and Q series I/O module
Yes. They have the same pin layout. More Details >>
- No:22774
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
KeepAlive setting for built-in Ethernet port in LCPU
The KeepAlive setting for the built-in Ethernet port in the L series is fixed. The setting is unchangeable. More Details >>
- No:22760
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
QnA-compatible 3E frame command for built-in Ethernet port in LCPU
The built-in Ethernet port in the L series CPU is not compatible with a multiple-block batch read command (0406) of the MC protocol. Executable commands are ... More Details >>
- No:22726
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
351-360 of Total 1023