FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Regarding protocol mixing in Serial Communication
It is not possible to connect multiple devices with different communication speeds and parities. More Details >>
- No:45480
- Release Date:2025/11/12 13:54
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Using Q series terminal blocks and connectors with MELSEC iQ-R series modules
You can use a Q series 18-point screw terminal block with a MELSEC iQ-R series terminal block type I/O module or analog module. For a 40-pin connector type ... More Details >>
- No:22474
- Release Date:2018/09/03 17:28
- Update:2018/09/19 14:37
- Category: MELSEC iQ-R Series
-
The number of modules that can be synchronized is as follows. - In single CPU system configuration: 64 modules - In multiple CPU system configuration: 57 t... More Details >>
- No:22496
- Release Date:2018/09/03 17:28
- Update:2018/09/21 17:15
- Category: MELSEC iQ-R Series
-
Although it depends on interrupt factors, the overhead time before startup becomes 10.8 to 23.8 [us] and the time after startup becomes 6.5 to 17.4 [us]. More Details >>
- No:22499
- Release Date:2018/09/03 17:28
- Update:2018/09/20 12:14
- Category: MELSEC iQ-R Series
-
How to write to file registers in Q series
Specify the file in the Write to PLC window and execute writing. More Details >>
- No:22585
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
PLC write not possible due to memory overload
If comments cannot be stored in the program memory, write them in the standard ROM or a memory card. Calculate the memory capacity in GX Works2 or GX Develo... More Details >>
- No:22595
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:49
- Category: MELSEC-Q Series
-
Procedure for developing programs
It is necessary to install a development environment (Tornado or Wind River Workbench) and set parameters using the Setting/monitoring tools for the C Cont... More Details >>
- No:22600
- Release Date:2018/09/03 17:29
- Update:2018/09/21 18:52
- Category: MELSEC-Q Series
-
The numbers of POUs and steps of "Allocate Memory for 'Online Change'" in GX Works2
The maximum number of steps that an online change can process at a time is 512. More Details >>
- No:22672
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
How to read comments in the standard ROM with GX Works2
Select [Target Memory] -> [Standard ROM] in the Read from PLC window. More Details >>
- No:22673
- Release Date:2018/09/03 17:29
- Update:2018/09/21 14:05
- Category: MELSEC-Q Series
-
Whether or not device indirect specifications in structured ladder programs are allowed
Indirect specifications with "@" cannot be used in structured ladder programs and the Structured Text. Use indirect specifications in a ladder language program. More Details >>
- No:22697
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
381-390 of Total 1023