Copying device comments in GX Works2
Select a device comment in the project view and select "Copy" from the right-click menu. More Details >>
- No:22950
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Can I open a program created with GX Works2 in GX Developer?
You cannot open a program in the file format for GX Works2. When saving a project with GX Works2, save it in the format for GX Developer.(This is possible on... More Details >>
- No:22956
- Release Date:2018/09/03 17:31
- Category: Engineering Software
-
Links with a CC-Link local station cannot be made
Check the following points. (1) CC-Link cables have been properly connected. (2) Station numbers and the transmission speed have been correctly set. (3)... More Details >>
- No:23033
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:22
- Category: Network related products
-
Connecting AJ65BT-R2N to a GOT
Yes.When connecting a GOT, set the mode setting switch of AJ65BT-R2N to "5" (MELSOFT connection mode). More Details >>
- No:23047
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
- Category: Network related products
-
You can set the parameters of the FL-net interface module with the data operation of the intelligent function module. For details and operation procedure of... More Details >>
- No:23084
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:19
- Category: Network related products
-
Use of latched (battery backed) type auxiliary relay
If the OUT instruction using a latched (battery backed) type auxiliary relay number exists in a sequence program, the information held may be overwritten by ... More Details >>
- No:24877
- Release Date:2019/04/15 08:07
- Category: MELSEC-F Series , Main Unit
-
Output numbers of the FX programmable controllers
Since they are octal, the number after Y7 is Y10 and after Y77 is Y100. More Details >>
- No:24946
- Release Date:2019/04/18 14:26
- Category: MELSEC-F Series
-
Connection of the FX3GC series and FX3U-ENET-ADP
Since the FX3U-ENET-ADP can be connected directly to the FX3GC series, optional equipment is not required. * When the FX3U-ENET-ADP is used with other spe... More Details >>
- No:24976
- Release Date:2019/04/23 07:20
- Category: MELSEC-F Series , Main Unit , Network/Communication
-
Regarding input of Differential Driver Output Type
It does not. The built-in high-speed counter function of the FX5U/FX5UC CPU module does not support DC5V input. DC5V input can be achieved by adding BUS con... More Details >>