      Terminating resistors for RS-485 communication of QJ71C24N The resistance value is 110 ohm, 1/2 W. More Details >> - No:22978
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:48
- Category: Network related products
 
- 
      How to set the numbers of occupied stations for CC-Link local stations Set the number of occupied stations for a CC-Link local station using the programming tool, GX Developer or GX Works2. Set the number for "Number of Occupied... More Details >> - No:22980
- Release Date:2018/09/03 17:31
- Category: Network related products
 
- 
      How to check errors in a CC-Link master station When an error has occurred in the master station (including the standby master station), the data link control cannot be performed, and you cannot check erro... More Details >> - No:23078
- Release Date:2018/09/03 17:31
- Category: Network related products
 
- 
      Modules that support differential line driver outputs The FX3U-2HSY-ADP, FX2N-10PG support differential line driver outputs. More Details >> - No:24691
- Release Date:2019/02/27 08:56
- Update:2023/02/15 13:09
- Category: MELSEC-F Series , Positioning Control
 
- 
      Terminal blocks for the MELSEC-F series Whether the terminal block is removable or not differs depending on the series. Types of the terminal blocks for the MELSEC-F series main units are as follow... More Details >> - No:24774
- Release Date:2019/02/27 15:34
- Category: MELSEC-F Series , Main Unit
 
- 
      Setting day of the week when using the TWR instruction (FX3 series) Day of week is automatically set. When data written to the data register for storing day-of-the-week data is within the setting range (K = 0 to 6), the day ... More Details >> - No:24777
- Release Date:2019/02/27 15:57
- Category: MELSEC-F Series , Main Unit
 
- 
      24+ terminal connection of an extension block For AC power supply type, connect the 24+ terminal of an extension block to the 24+ terminal of a main unit. For DC power supply type, connect the 24+ termi... More Details >> - No:24786
- Release Date:2019/02/28 09:06
- Category: MELSEC-F Series , Main Unit , I/O Extension
 
- 
      MELSOFT connection of the FX3U-ENET-ADP Ethernet communication special adapter Up to 4 connections can be opened. More Details >> - No:24903
- Release Date:2019/04/15 11:31
- Category: MELSEC-F Series , Network/Communication
 
- 
      Operation speed change during a positioning operation of the FX3U-1PG Yes, it is possible. Write a new value to the operation speed change value (BFM#56, #55) during the positioning operation. * After the operation speed chang... More Details >> - No:24927
- Release Date:2019/04/17 11:42
- Category: MELSEC-F Series , Positioning Control
 
- 
      Pulse output system of the FX3U-1PG pulse output block Forward (FP) and reverse (RP) pulse or pulse (PLS) with direction (DIR) can be selected. More Details >> - No:24957
- Release Date:2019/04/18 14:28
- Category: MELSEC-F Series , Positioning Control
 