FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Yes. As a guide, the processing time is shown below.For the logging condition, refer to figure 1 below. - For 16 devices: 2 ms - For 64 devices: 6 ms More Details >>
- No:22829
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:33
- Category: MELSEC-L Series
-
Use of END cover with the branch module and extension module
Use an END cover applicable to the following. - The L6EC whose serial number (first six digits) is "*****2" or later- END cover with ERR terminal (optional i... More Details >>
- No:22815
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Execution of the SOCRMODE instruction in the same connection during socket communication of LCPU
It can be executed for the same connection number. When data exist in the socket communication receive data area and the SOCRMODE instruction is executed, va... More Details >>
- No:22771
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
A password can be set. - Use the file password 32 function.- Number of characters: 4 to 32 (alphanumeric and special characters, case-sensitive)- Disabled op... More Details >>
- No:22810
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Configuration of simple PLC communication function using LCPU
At least one L series CPU is necessary when using the simple PLC communication function. More Details >>
- No:22747
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
The error code "2400" is "FILE SET ERROR". This error may be caused when the file specified with a parameter does not exist. The individual information param... More Details >>
- No:22729
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Terminating resistors for RS-485 communication of LJ71C24
The resistance value is 110 ohm, 1/2 W. More Details >>
- No:22999
- Release Date:2018/09/03 17:31
- Update:2018/10/03 15:25
- Category: Network related products
-
Necessities for the execution environment of MX Component
Both the developed software and MX Component must be installed. More Details >>
- No:22557
- Release Date:2018/09/03 17:29
- Update:2018/09/20 15:53
- Category: MELSEC-Q Series
-
The "S/S" terminal is used to switch the input type (sink input and source input). For the source input, connect the "S/S" terminal to the "0V" terminal, a... More Details >>
- No:22255
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
Regarding the simultaneous use of Simple CPU Communication and FX5-CCLGN-MS MELSOFT Connection
Can be used simultaneously. More Details >>
- No:39285
- Release Date:2023/01/12 16:50
- Category: MELSEC iQ-F Series , Network/Communication
461-470 of Total 1023