Regarding how to change the averaging processing of FX5-4AD-ADP programmatically
It is possible to change the number of counts for count averaging in a program. Set the module parameter Basic settings to "Set A/D conversion method" to Di... More Details >>
- No:44618
- Release Date:2024/11/28 16:13
- Category: MELSEC iQ-F Series , Analog
-
Error in simulation in GX Works2
This problem can be workarounded by upgrading software products made by other companies to the latest version or uninstalling them.For more details, refer to... More Details >>
- No:22570
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Memory allocation for online change
The scan time may be substantially longer. Continue the operation if there is no problem with the longer scan time. More Details >>
- No:22575
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:01
- Category: MELSEC-Q Series
-
How to use LCPU connector terminals
The LCPU connector terminals can be used as terminals for built-in I/O function. The setting of the built-in I/O function can be configured with the paramete... More Details >>
- No:22796
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Program by program difference in comments on display
There are two types of device comments: "global device comment" and "local device comment". Device comments can be displayed in the ladder editor and Zoom... More Details >>
- No:22868
- Release Date:2018/09/03 17:30
- Update:2018/09/22 14:40
- Category: Engineering Software
-
GX Developer's compatibility with LJ71E71-100
GX Developer does not support LJ71E71-100. Use GX Works2. More Details >>
- No:22911
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
I cannot open a project file of PX Developer.
When the total number of characters in the drive/path and project name exceeds 149 one-byte characters (74 two-byte characters), the message "The drive path ... More Details >>
- No:22947
- Release Date:2018/09/03 17:30
- Update:2018/09/25 10:58
- Category: Engineering Software
-
Receiving back (echoing back) the same data sent from QJ71C24N
When data is sent from the RS-422/485 interface through RS-485 (2-wire type) communication and the same data comes back to RDA or RDB, we call it echo back. ... More Details >>
- No:23000
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:44
- Category: Network related products
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
- Category: Network related products
-
RS-485 connection between LJ71C24 and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:23048
- Release Date:2018/09/03 17:31
- Category: Network related products
511-520 of Total 1023