FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
MC protocol supported by the FX3U-ENET-L
The frame typesupported byMC protocol is equivalent to A-compatible 1E frame. More Details >>
- No:24702
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Network/Communication
-
Necessity of a battery when a memory cassette is used
A battery is not required when a memory cassette is used. This is because the sequence programsstored in the memory cassette, exceptfor RAM memory cassette, ... More Details >>
- No:24770
- Release Date:2019/02/27 15:00
- Category: MELSEC-F Series , Main Unit , Accessories
-
The external and mounting dimensions of the FX2N-1PG and the FX3U-1PG are identical. However, the electrical specifications and connectable FX programmable c... More Details >>
- No:24905
- Release Date:2019/04/15 11:31
- Category: MELSEC-F Series , Positioning Control
-
Cable provided with the FX2N series extension unit
It is available as a repair part. Please consult with localMitsubishi Electric representative. More Details >>
- No:24916
- Release Date:2019/04/17 11:40
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
Connection of the FX3G series and the GT1020/GT1030 series (5 V type)
Only one GT1020/GT1030 series (5 V type) can be connected to the FX3G series. To connect two GOTs, select the GT1020/GT1030 series (24 V type). More Details >>
- No:24969
- Release Date:2019/04/23 07:19
- Category: MELSEC-F Series , Main Unit
-
Types of the ports built in the FX programmable controllers
There are RS422 × 1ch for the FX1S/FX1N/FX1NC/FX2N/FX2NC/FX3U/FX3UC series and RS422 × 1ch and USB × 1ch for the FX3G/FX3GC series. More Details >>
- No:24971
- Release Date:2019/04/23 07:19
- Category: MELSEC-F Series , Main Unit
-
Output frequency of the FX3U-1PG pulse output block
It is from 1 Hz to 200 kHz. More Details >>
- No:24981
- Release Date:2019/04/23 07:21
- Category: MELSEC-F Series , Positioning Control
-
Changing the JOG speed in the FX3U-20SSC-H
Since the JOG speed is the positioning parameter, turn off and on the positioning parameter enable command (X-axis: BFM#519.b4, Y-axis: BFM#619.b4) to enable... More Details >>
- No:24987
- Release Date:2019/04/23 07:22
- Category: MELSEC-F Series , Positioning Control
-
The FX2N-16CCL-M cannot be set as the master station in the parameter setting. Use the FROM/TO instructions and setin the program. More Details >>
- No:25001
- Release Date:2019/04/23 10:39
- Category: MELSEC-F Series , Network/Communication
-
Regarding "_ U" in Application Instruction
It means an instruction that handles BIN 16 bit and BIN 32 bit unsigned data. Example:ADD _ U More Details >>
- No:39295
- Release Date:2023/02/13 16:37
- Category: MELSEC iQ-F Series , CPU Module
571-580 of Total 1023