Regarding the connection between FX5-CCLGN-MS and NZ2GN2S-60AD4
Available. More Details >>
- No:39279
- Release Date:2023/01/12 16:47
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding the connection between FX5-CCLGN-MS and SLMP-compatible devices
The SLMP communication frames supported by the FX5-CCLGN-MS are 3E and 4E frames. When SLMP communication is performed from an SLMP-compatible device to the... More Details >>
- No:39280
- Release Date:2023/01/12 16:48
- Category: MELSEC iQ-F Series , Network/Communication
-
Regarding the possibility of adding an additional module to the FX5S CPU module
You cannot. The FX5S CPU module does not support the connection of an additional module (I/O module, Intelligent function module, FX5 safety extension modul... More Details >>
- No:39339
- Release Date:2023/02/14 17:28
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding Instruction processing time when the program capacity: 128 K steps are set
LD instruction: 0.35 μs, MOV instruction: 0.779 μs. For other instructions, see the manual below. MELSEC iQ-F FX5 Programming Manual (Instructions, Standa... More Details >>
- No:39362
- Release Date:2023/01/12 17:12
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding using the 2nsec Clock Timer
The value of n can be set in SD414, and the range is from K1 to K32767. (Default value: K30) If n=K1, it is a 2-second clock timer with 1 second ON/1 second... More Details >>
- No:40019
- Release Date:2023/08/24 14:29
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding enclosed power cable for input module and input/output module for extension connector type
The FX2NC-100BPCB is included with the following products. CPU Modules: FX5UC-32 MT/D, FX5UC-64 MT/D, FX5UC-96 MT/D More Details >>
- No:40047
- Release Date:2023/08/24 16:30
- Update:2024/05/09 09:59
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding restrictions on the external input/output forced ON/OFF function
The following restrictions apply to the external input/output forced ON/OFF function. ・Since RUN contact setting is RUN/STOP by external signal, forced ON/O... More Details >>
- No:44332
- Release Date:2024/03/20 12:58
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding the differences between the FX5-2HC/ES and the conventional FX3U-2HC input formats
The FX5-2HC/ES supports differential line drivers (5 V) only. The FX3U-2HC supports open collectors (24 V/12 V/5 V) and differential line drivers (5 V). ... More Details >>
- No:44338
- Release Date:2024/03/26 09:02
- Category: MELSEC iQ-F Series , High-Speed Counter
-
How to check the scan time with GX Works3
You can check the processing time and scan time of the program currently being executed in "Program List Monitor". [Online] -> [Monitor] -> [Program... More Details >>
- No:22458
- Release Date:2018/09/03 17:28
- Update:2018/09/19 11:51
- Category: MELSEC iQ-R Series
-
PLC type change in GX Developer
Follow the steps below and then execute PLC type change.- On the menu of GX Developer, select [Online] -> [Monitor] -> [Stop Monitoring (All Windows)],... More Details >>
- No:22522
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series