Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
When the block number of the file register (R) is saved and stored, the overhead time becomes 35.9 [us]. When the number of the file register is not saved o... More Details >>
- No:22465
- Release Date:2018/09/03 17:28
- Update:2018/09/19 11:57
- Category: MELSEC iQ-R Series
-
Pulse width with which the QX42 recognizes all pulses
Maximum scan time (10 ms) + Response time (10 ms) = Pulse width with which the module recognizes all pulses (20 ms) More Details >>
- No:22720
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Synchronizing the internal clock of a universal model QCPU
- When a built-in Ethernet port QCPU is used You can synchronize it with the server using the time setting function. -When a module other than built-in ... More Details >>
- No:22723
- Release Date:2018/09/03 17:29
- Update:2018/09/21 15:53
- Category: MELSEC-Q Series
-
Versions of built-in Ethernet port LCPU compatible with SNTP function
The initial version and subsequent versions of L series CPU support the SNTP function. More Details >>
- No:22769
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
How to set the numbers of occupied stations for CC-Link local stations
Set the number of occupied stations for a CC-Link local station using the programming tool, GX Developer or GX Works2. Set the number for "Number of Occupied... More Details >>
- No:22980
- Release Date:2018/09/03 17:31
- Category: Network related products
-
GX Developer's compatibility with 64-bit Windows 7
GX Developer Version 8.98C or later supports 64-bit Windows 7. To install GX Developer to a Windows 7-based personal computer, refer to the following techni... More Details >>
- No:22501
- Release Date:2018/09/03 17:28
- Update:2018/09/20 12:19
- Category: MELSEC-Q Series
-
Compatibility between the A series modules and Q series modules
When an ACPU module is replaced with a QCPU module, programs for the ACPU module can be used by changing the PLC type in GX Developer. However, the programs ... More Details >>
- No:22696
- Release Date:2018/09/03 17:29
- Update:2018/09/21 14:21
- Category: MELSEC-Q Series
-
FNC connector pin layout in L series I/O module and Q series I/O module
Yes. They have the same pin layout. More Details >>
- No:22774
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Sample comments for special relays/registers
Files are stored as sample comments when GX Developer is installed. Read a comment from the project data of sample comments to a user project and copy a port... More Details >>
- No:22837
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Connecting special adapters to the FX3G series