FAQ


FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Editable range of Inline Structured Texts
Up to 2048 characters can be entered in the inline Structured Text box. The limit cannot be increased. Note that a line break is counted as 2 characters. More Details >>
- No:22852
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
CPU operation when the time setting failed
When an error occurs, the operation can be stopped or continued according to the "At Error Occurrence" setting.(The default is "Continue".) More Details >>
- No:22828
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Number of data sampling points in LCPU logging function
Up to 1280 points. (128 points per setting, and up to 10 data logging settings) More Details >>
- No:22805
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
How to use L series extension modules
The extension module is used to configure the extension block when 10 modules or more are mounted to LCPU. Connect the branch module and the extension module... More Details >>
- No:22738
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
GX Developer's compatibility with 32-bit Windows 7
GX Developer Version 8.91V or later supports 32-bit Windows 7. More Details >>
- No:22660
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Use SP.FWRITE instruction to save the data to an ATA card in CSV format.For Q00UJCPU, Q00UCPU, and Q01UCPU, however, memory cards cannot be used thus data ca... More Details >>
- No:22652
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
GX Works2's compatibility with Monitor (write mode)
From version 1.62Q, GX Works2 supports Monitor (write mode). Pressing Shift+F4 allows an online change. More Details >>
- No:22612
- Release Date:2018/09/03 17:29
- Update:2018/09/20 18:18
- Category: MELSEC-Q Series
-
Reading and writing bits/words using the FL-net (OPCN-2) interface module
The parameters and auto refresh settings for the FL-net (OPCN-2) interface module cannot be made using the Network Parameter items in GX Developer.Set those ... More Details >>
- No:22597
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
SD520 stores the current scan time in 1 ms units. More Details >>
- No:22556
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
It is an embedded RTOS (real-time OS) developed by Wind River, which is proven worldwide as reliable and stable.The version of the operation system installed... More Details >>
- No:22544
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
661-670 of Total 1023