FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Operation performed when file registers are read
Checking "Device Memory" does not read file registers. Switch the Target Memory for "PLC Data" to "Standard RAM" and check "File Register" in the Read from P... More Details >>
- No:22835
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
CPU operation when the time setting failed
When an error occurs, the operation can be stopped or continued according to the "At Error Occurrence" setting.(The default is "Continue".) More Details >>
- No:22828
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Connected position of branch module and extension module
The position to connect the branch module and extension module is as follows. More Details >>
- No:22814
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:27
- Category: MELSEC-L Series
-
I/O assignment for additional modules connected to LCPU
In L02CPU(-P), the start I/O number of the additional module begins from 10H. In L26CPU-(P)BT, the number begins from 30H. More Details >>
- No:22808
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
How to use LCPU connector terminals
The LCPU connector terminals can be used as terminals for built-in I/O function. The setting of the built-in I/O function can be configured with the paramete... More Details >>
- No:22796
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
CSV file storage timing in L series logging function
No. More Details >>
- No:22793
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
GX Developer Version 8.89T or later is supported.There are restrictions in some functions. For the details, refer to "Precautions on L Series Modules" in ... More Details >>
- No:22792
- Release Date:2018/09/03 17:30
- Update:2018/10/03 16:26
- Category: MELSEC-L Series
-
SD1284 of LCPU with built-in Ethernet port
The bits 0 to F of the special register SD1284 (Open request signal) correspond to the connection numbers 1 to 16. When the open request is sent, the corresp... More Details >>
- No:22784
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Q6BAT. More Details >>
- No:22780
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
The conversion speed is as follows. - High speed: 20 microseconds per channel- Medium speed: 80 microseconds per channel- Low speed: 1 millisecond per channel More Details >>
- No:22776
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
661-670 of Total 983