FAQ within [ Programmable Controllers MELSEC ]
-
Using the email function of FX5-ENET, it is possible to send mail via a mail server. The email function is supported in the following versions. ・Hardware s... More Details >>
- No:40035
- Release Date:2023/08/24 15:40
- Update:2023/08/25 11:34
- Category: MELSEC iQ-F Series , Network/Communication
-
No. More Details >>
- No:22589
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:42
- Category: MELSEC-Q Series
-
Error in simulation in GX Works2
This problem can be workarounded by upgrading software products made by other companies to the latest version or uninstalling them.For more details, refer to... More Details >>
- No:22570
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Time out error in the communication test of MX Component
The possible causes are as follows. - Incorrect setting with a personal computer or an Ethernet interface module Check the IP address, network number, sta... More Details >>
- No:22934
- Release Date:2018/09/03 17:30
- Update:2018/09/25 09:49
- Category: Engineering Software
-
Regarding the method to check the scan time
The current value of the scan time is stored in the following special devices. Please monitor using GX Works3. ◇Scan information SD520 Current scan time (... More Details >>
- No:22289
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:20
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Reception data read request signal of QJ71C24N not turn ON
The default receive complete code is CR+LF (0DH, 0AH). The default received data count is 511 words. Hence, at their defaults, Reception data read request si... More Details >>
- No:22984
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:22
- Category: Network related products
-
The error code "2100" is "SP.UNIT LAY ERR.". This error may be caused by one of the following factors. (1) In the I/O assignment setting of the PLC parame... More Details >>
- No:22650
- Release Date:2018/09/03 17:29
- Update:2018/09/21 11:47
- Category: MELSEC-Q Series
-
Regarding maximum number of connections for the simple CPU communication function
The maximum number of connections for the simple CPU communication function of FX5 CPU module is 16 for FX5U/FX5UC CPU module and 8 for FX5UJ/FX5S CPU module... More Details >>
- No:40032
- Release Date:2023/08/24 15:37
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Checking the amount of free space of the memory in GX Developer/GX Works2
Select [Tool] -> [Confirm Memory Size] to check the amount. More Details >>
- No:22851
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
The error code "2200" is "MISSING PARA.". The causes of the error are described below. (1) The necessary parameter file does not exist in all drives. (2) ... More Details >>