FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
The error code "4100" is "OPERATION ERROR". The error occurs when a number is divided by 0 (Divisor D6268 value is 0). Make modifications so that the divis... More Details >>
- No:22533
- Release Date:2018/09/03 17:28
- Update:2018/09/20 14:43
- Category: MELSEC-Q Series
-
Programmable controllers with no battery (MELSEC-F)
A battery is used for backing up program memory and latched device data and maintaining clock operation in the event of a power failure. The FX3S/FX3G/FX3G... More Details >>
- No:22259
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , Accessories
-
[F2-40BL] F1/F1J/F2 series, FX1/FX2/FX2C/FX2N series, and FX-20GM/E-20GM [FX1N-BAT] FX1N series* [FX3U-32BL] FX3G*/FX3GC/FX3U/FX3UC series and FX-30P [FX2N... More Details >>
- No:22282
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , Accessories
-
Error code "2200" in the universal model QCPU
The error code "2200" is "MISSING PARA.". The cause of the error is that a parameter file does not exist in all drives where parameters will be valid.As a re... More Details >>
- No:22614
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Regarding MODBUS/TCP communication of the built-in Ethernet port
When used as a master station, communication with a slave station can be performed using the simple CPU communication or the predefined protocol support func... More Details >>
- No:22302
- Release Date:2018/08/30 13:55
- Update:2022/12/22 08:52
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding how to check MAC Addresses
You can check the MAC address from the name plate on the side of the CPU module or by the Module diagnostics (CPU diagnostics) of GX Works3. More Details >>
- No:39294
- Release Date:2023/02/13 15:37
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Regarding the type of Ethernet connection cable
Ethernet standard-compatible cable, category 5 or higher (STP cable) can be used. *Straight cable can be used. When connecting directly to the computer, cr... More Details >>
- No:22295
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:23
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the maximum number of connections for MODBUS communication
32 stations can be connected when RS-485 port is used and only 1 station can be connected when RS-232 port is used. More Details >>
- No:22324
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:49
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Difference between GX Works2 and GX Developer
Main differences between GX Works2 and GX Developer are as follows:-The functions of GX Configurator and GX Simulator are integrated as GX Works2. No additio... More Details >>
- No:22503
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
961-970 of Total 1023