FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
How to use PWM output of LCPU built-in I/O
Set the PWM output-on-width and the PWM output cycle, and then execute a dedicated instruction "ICPWM instruction". More Details >>
- No:22757
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Simultaneous broadcast transmission setting for built-in Ethernet port LCPU
To send simultaneous broadcast using UDP, set the parameters as follows.- Destination IP Address: FF.FF.FF.FFh - Destination Port Number: Other than FFFFh (S... More Details >>
- No:22785
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Refresh timing of bit data and word data in the same CC-Link station
Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the ... More Details >>
- No:23058
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Number of points used for I/O assignment of L26CPU-(P)BT built-in CC-Link function
It is fixed to 32 points from 10 to 2F. More Details >>
- No:22777
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Built-in positioning function of LCPU
The positioning operation starts just in 30 microseconds, with a maximum high speed output of 200k pulses per second. S-curve acceleration/deceleration is al... More Details >>
- No:22790
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
How to obtain connectors used for L series connector type I/O modules
A connector is not included. The connector is obtained by user. A6CON1 (soldering connector, straight out type), A6CON2 (crimp connector, straight out type),... More Details >>
- No:22791
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Restriction on the use of CPU when branch module and extension module are used
Use L series CPU modules whose first 5 digits of the serial number are "13072" or later. More Details >>
- No:22800
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Detecting the number of disconnections when using QJ71E71-100
The number of disconnections detected can be checked by reading the buffer memory address 5203H (Disconnection detection count). Disconnections are detected ... More Details >>
- No:23003
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:49
- Category: Network related products
-
Effect on sequence scans in MELSECNET/H networks
It is necessary to reduce the link refresh time of the MELSECNET/H network in order to reduce the scan time. The link refresh time can be reduced by reducin... More Details >>
- No:23018
- Release Date:2018/09/03 17:31
- Update:2018/09/26 09:27
- Category: Network related products
-
Order in which a CC-Link master module and slave stations are connected
There is no restriction on the positions of a master station and slave stations where they are connected. (Stations are not required to be connected in order... More Details >>
- No:23041
- Release Date:2018/09/03 17:31
- Category: Network related products
1-10 of Total 1000